56
Options
UltraVoice (UV)
When wiring the Model UVTR to the Control Cabinet, the installer must follow
wiring instructions as in Figure 26 Transformer Rectifier Wiring to Control or
damage may occur to Control System and/or batteries.
Preparation
To wire the UVTR, do the following:
1. Refer to “Figure 9 Typical Siren” on page 32 and “Figure 31 UVTR
Transformer” on page 78.
2. Remove the UVTR transformer from its shipping crate and stand the transformer
on its top to expose the inspection covers located on the bottom side.
3. Remove the four 3/8 inch hex head bolts that secure the inspection covers and
remove the inspection covers from the transformer.
4. From the inside of the transformer, pull the four lines:
210-264 Vac Input
• 1 Common
• 4 (60 Hz) or 5 (50 Hz)
120 Vac Output
• 1 Common
• 2-120 Vac (60 Hz) or 3-120 Vac (50 Hz)
5. Punch or drill the plate, use one ½ inch conduit for ac in and one 1 inch conduit
for 120 V and 24 V out to the controller.
6. Install a 1 inch 45 degree Liquid-Tight connector into the 1 inch opening on the
transformer. Face the connector to the rear of the transformer and tighten the 1
inch lock ring. Put a 1 inch plastic bushing over the exposed thread end on the 1
inch connector.
7. Cut a section of 1 inch Seal-Tight, 7 inches in length. This provides raceway for
the 24 Vdc secondary and for Control Cabinet 120 Vac input.
8. Cut a section of ½ inch Seal-Tight 18 inches in length. This provides A/C input
voltage from the ac disconnect to the transformer. 120 Vac output taps in the
UVTR are used to provide ac voltage to the Control Cabinet. Run the Seal-Tight
between the UVTR and the Control Cabinet.
Summary of Contents for ultravoice UV
Page 42: ...42 Installation UltraVoice UV Figure 15 Omni Antenna Installation Example...
Page 43: ...43 Installation Installation Operation and Service Manual Figure 16 Antenna Grounding...
Page 71: ...71 Appendix C Drawings Figure 25 UV Controller Two way Radio Wiring Diagram...
Page 72: ...72 Figure 26 UVTD IP Broadband Wiring Diagram...