9
Installation and Maintenance Instructions
Selectone Model PS600
During Power Failure
Voltage:
26.4 Vdc no load
24 Vdc nominal
Current:
6 A maximum
(25° C)
*(see note)
Output Circuits
(Non-Power-Limited)
6 A at 24 Vdc resistive
Dry Contact Closure
of Trouble Out Relay
Connect to power limited circuits
ac Fail Relay
2 A, 120 Vac/28 Vdc
Battery Trouble Relay 2 A, 120 Vac/28 Vdc
Battery Package
Number of Batteries
2 connected in series
Battery Voltage
12 V each (24 V total)
Capacity
12 Ah
Type
Sealed, lead-acid gelled electrolyte
Recharge Time
48 hours (after complete discharge)
Charging Current
1.25 A maximum
Physical
Dimensions (HWD)
15.50 in x 12.50 in x 4.50 in
Weight
13 lb (without batteries)
Operating Temp. Range 0° C to + 49° C
*Battery current capacity changes throughout the operating temperature range.