19
Programming
Signaling Standalone Manual
Federal Signal
www.fedsig.com
NOTE
: There are over 160 standard messages included on the SD card.
See “Appendix A
Standard DV Messages” on page 43 for a complete list.
Invalid WAV File Control Commands
Examples of illegal WAV file Control Commands.
Table 12 Examples of Illegal WAV Files
Invalid WAV
Files Control
Commands
Why
*1
Missing end of frame character. The entry is discarded 5 seconds
after 1 is received.
111*
Missing start of frame character before 111. The entry is discarded
5 seconds after * is received.
*1#
# is not a legal framing character for WAV file control and cannot
be used in a command with a * framing character. The entry is
discarded 5 seconds after # is received.
#1*1*
# is not a valid WAV file framing character. #1 is discarded, but *1* is
accepted to activate WAV file number one.
#1#
#1# is a Function Control command that activates Function #1 and is
not a WAV file command.
*1A*
A is not a legal digit. The entry is discarded 5 seconds after * is
received.
*5000*
Valid WAV file index numbers are limited to 1-4093. The entry is
discarded 5 seconds after * is received.
Function Control Commands
Function Control commands are used to activate functions that have been preconfigured
into the Informer. Functions can be configured to control audio volume, activate relay
outputs, play tones, and play WAV files. Functions configured with Commander
®
can also
include delays and repeat loops.
The input functions can be configured on the Informer’s web page and activated by
initiating local digital inputs on the Informer.
Configuring Informers Using the Web Interface
Informer products can operate as autonomous devices controlled by contact closures
without connecting to a network server or becoming part of a supervised network with
remote configuration, control, and status monitoring. Use the Informer’s internal web
server to configure network settings, volume control, remote input configuration, access
security, Modbus®, and SIP interfaces. More advanced configuration and programming
require Federal Signal’s Commander software application and SmartMsg Centerpoint