Limited Warranty: 

This product’s limited warranty can be found at www.fedsig.com/SSG-Warranty

SAFETY MESSAGES TO INSTALLERS AND USERS

 

: Products should be installed by a licensed electrician and follow 

all safety instructions. Failure to do so may result in property damage, serious injury, or death.

• 

Read and understand all instructions before installing or operating this equipment.

• 

To avoid electrical shock hazards, do not connect wires when power is applied. Failure to observe this warning may 

lead to serious injury or death.

• 

Never alter the unit in any manner. Safety in hazardous locations may be endangered if additional openings or other 

alterations are made in units specifically designed for use in these locations.

• 

Do not connect this station to the system when power is on.

• 

After installation, ensure that all threaded joints are properly tightened.

• 

Keep the unit tightly closed when in operation.

• 

After installation, test the station and the system to ensure that it is operating properly.

• 

After testing is complete, provide a copy of this instruction sheet to all personnel.

• 

Establish a procedure to routinely check the station and system for proper activation and operation.

Failure to follow all safety precautions and instructions may result in property damage, serious injury, or death.

Certifications

ATEX and IECEx Certification Information:

Certificate Nos.

ATEX Cert No.: DEMKO 19 ATEX 1939X 

IECEx Cert No.: IECEx UL 19.0074X

ATEX coding

 II 2 G D

Protection

II 2 G Ex db eb mb IIC T4 Gb (Tamb= -40°C to +70°C) 

CP-BG models: II 2 D Ex tb IIIC T100°C Db IP66 

CP-PB models: II 2 D Ex tb IIIC T100°C Db IP65

EN60079-0, EN60079-1, EN60079-7, EN60079-18, EN60079-31, IEC60079-0, IEC 60079-1, IEC60079-7, IEC60079-18, 

IEC60079-31

Refer to Certificates for specific standard versions.

Specific Conditions of Use

1. 

The equipment has an optional protective non-metallic cover that may provide a potential electrostatic charging 

hazard.

Manual Call Point

Pushbutton and Break Glass Stations for Use in 

Hazardous Locations

25500424 Rev A2 0522

Summary of Contents for CP-BG Series

Page 1: ...nstallation test the station and the system to ensure that it is operating properly After testing is complete provide a copy of this instruction sheet to all personnel Establish a procedure to routinely check the station and system for proper activation and operation Failure to follow all safety precautions and instructions may result in property damage serious injury or death Certifications ATEX ...

Page 2: ...4 11 certification 3 To enable correct installation and operation review all sections in this manual 25500424A for all technical installation and maintenance data UL C UL Signaling Certification Information Model CP PB Series 1 UL Certification applies to push button models series CP PB Series only CP BG models are not UL C UL Listed 2 For use in Non Monitoring NM and Self Monitoring SM Emergency ...

Page 3: ...reinforced polyester GRP thermoset plastic housing and faceplate for corrosion resistance 40 C to 70 C ambient operational coverage Static dissipative GRP housings and faceplates One or two switches available two switches unavailable with LED option factory installed Three M20 or 1 2 inch NPT threaded entryways 180 rotatable rear housing with respect to front housing for top or bottom dual conduit...

Page 4: ...ed 6 V 12 V 24 V or 48 V LED bi color status indicator High impact resistant clear polycarbonate cover flap with or without various instructional labels e g LIFT COVER BREAK GLASS TO ACTIVATE on interior face of the cover flap Side mounted stainless steel break glass hammer bar on BG stations Single and dual switches EN54 11 certified Break Glass stations Federal Signal Manual Call Point Station m...

Page 5: ...ointer Figure 1 Removing the keyway UNLOOSENM4SETSCREW TOREMOVERESET KEYWAYANDBEARING WASHERIFPRESENT UNLOOSENTWOM4 CAPTIVATEDSCREWS REMOVE BUTTON ANDSCREW Figure2 ACTUATORSPRING PIVOTBOSSES CLEAR ACTUATOR CYLINDER SPRINGLOADED BUTTONSTEM ASSEMBLY 3 Loosen the two M4 Philips head screws at the 3 00 and 9 00 positions on the faceplate and remove the faceplate NOTE These two screws are captivated to...

Page 6: ...r Chamber Access All models of the Call Point station have the same rear chamber access method for internal wiring management mounting the unit to a vertical wall surface and general maintenance routine inspection To access the rear chamber 1 Loosen the four captivated socket head cap M4 screws by using a M3 hex wrench at each of the front corners of the device 2 Carefully pull away the front hous...

Page 7: ... accordance with the installation instructions and local jurisdictions and codes Use installer supplied fasteners suitable for the mounting surface All models of the Call Point station have the same rear chamber access to four corner oval shaped holes for mounting the station to a rigid vertical wall surface The devices may be mounted by using four M6 metric threaded fasteners or four 1 4 inch or ...

Page 8: ...n corrosive environment applications mounting the station to a rigid surface Ensure that all cable glands and stopping plugs are certified with a suitable sealing washer o ring to ensure the NEMA IP rating of the station The internal earth ground terminal must be used for equipment grounding where and when required Internal Rear Chamber Wiring SHOCK HAZARD To avoid electrical shock hazards do not ...

Page 9: ...s on the aluminum mounting bracket and remove it from the rear housing taking care as it still remains directly wired to the front housing assembly 2 Strip the incoming wiring leads to the station to the appropriate length as noted above depending on wiring block configuration NOTE Ensure that the incoming lead lengths into the station meet the required national and local regulations codes and als...

Page 10: ...pull double throw switch device on a double pull double throw device input terminals 6 7 and 8 are used as secondary inputs with common Figure 8 Standard SPDT switch wiring Figure 9 Standard DPDT switch wiring Optional EOL Diode and Series Resistor Module Install and Wiring SPDT and DPDT devices For the SPDT and DPDT models with optional field installed EOL or Series Resistor Module s please note ...

Page 11: ...ctivation current draw of 13 mA of the red alarm state LED function will not interfere with the alarm notification panel If it does the hookup of the red LED lead must be disconnected from the terminations block Failure to observe this warning may lead to property damage serious injury or death When using with a fire alarm control panel the panel is to be limited to 5 A maximum An LED EOL or serie...

Page 12: ...87 50 990 00 1320 00 3300 411 41 767 44 1164 71 1650 00 4700 427 27 824 56 1301 54 1938 75 5000 429 62 833 33 1323 53 1987 95 5600 433 61 848 48 1362 16 2076 40 10000 448 90 909 09 1525 42 2481 20 12000 452 29 923 08 1565 22 2588 24 15000 455 72 937 50 1607 14 2704 92 22000 460 17 956 52 1663 87 2869 57 33000 463 40 970 59 1706 90 3000 00 47000 465 35 979 17 1733 61 3083 50 Electrical Specificatio...

Page 13: ...TATE ACTIVATION INDICATOR STATUS POSITIONS VISUAL ACTIVATION INDICATOR WITH RESET KEYWAY ALARM STATEACTIVATED Reset Test For the manual pushbutton stations resetting is accomplished by rotating the activation indicator approximately 60 counterclockwise by use of a reset keyway that is mated to the activation indicator Upon rotating counterclockwise the pushbutton knob along with the internal switc...

Page 14: ...ons resetting is accomplished by either of two methods following the previously mentioned two methods of activating the stations 1 To replace the broken glass panel follow the directions on page 16 Once replaced the internal mechanism should be back to its NORMAL standby position as noted on the station s front faceplate Ensure that the proper switch deactivation has occurred and that the associat...

Page 15: ...are some important safety instructions and precautions you should follow with regards to all instructions within this manual Read and understand all instructions before operating this system If you acquired a significant quantity of units then it is recommended that spares be made available Any maintenance to the Call Points station must be done with the power turned off Any maintenance to the Cal...

Page 16: ... this manual to do so Replacing the Break Glass Panel CP BG units To replace a broken glass panel on the station CUTTING HAZARD Safety gloves are required when accessing the internal front chamber with a broken glass panel in order to prevent wounds 1 Carefully remove the front faceplate to access the front chamber Caution should be taken as sharp glass pieces may be evident which may result in wo...

Page 17: ...ODELS Installing Servicing the Reset Keyway The reset keyway is factory attached on the CP PB and CP BG stations On the CP BG x x x xxx xx 2 E54 11 approved stations it is provided separately to be used only as a discrete standalone key On these models the key should not be permanently installed for EN 54 11 installations and shall be used only for test purposes Its purpose is twofold 1 Provide a ...

Page 18: ...certified models To remove or remove reattach a cover flap 1 Remove the front faceplate per directions found earlier in Call Point Front Chamber Access on page 5 Place the two stainless steel pivot pins of the cover flap within the slot found on the backside of the faceplate and rotate the cover 180 to snap the cover flap onto the front face 2 Reattach the faceplate See Opening Closing the Call Po...

Page 19: ...ies resistor along with two wire ties Tools needed after internal access Wire cutter 1 Philips screwdriver To service the module 1 Ensure that the power is off and the station is in NORMAL mode 2 Open the station so that the front housing s internal side is shown see Opening Closing the Call Point for Internal Access on page 4 along with the internal side of the rear housing Remove the three screw...

Page 20: ...d reseat the module in its reliefs screw it in place and try again e After confirming that the station actuates properly use the two wire ties provided within the kit to bundle and tie the switch wires to the LED wires in the locations where the previous wire ties were Clip off the excess of the wire tie so that it cannot interfere with the switch s actuation 8 Reattach the front housing to the re...

Page 21: ...e station faceplate s designated label area Make sure the application area is free from any dirt smudges or oil prior to application Figure 31 Installing the label OPTIONALINDIVIDUALSTAINLESSSTEELFACEPLATELABEL SUPPLIEDASSERVICE ACCESSORYPART PEELOFFLABELLINER FORADHESIVEBACKED APPLICATIONTO FACEPLATEFRONT Installing Servicing the Optional Stainless Steel Custom Duty Plate NOTE The stainless steel...

Page 22: ...tion of hazardous atmospheres disconnect the fixture from the supply circuit before opening EXPLOSION HAZARD Substitution of any component may impair suitability for Class I Division 2 Service Technical Assistance Contact our Technical Support Team at 1 708 587 3587 or signalsupport fedsig com Repair Service A return authorization is required Contact your Authorized Distributor or Federal Signal C...

Page 23: ...d with 24V LED option 2 2KΩ 2200 2 4KΩ 2400 3 3KΩ 3300 also used with 48V LED option 3 6KΩ 3600 4 7KΩ 4700 5 6KΩ 5600 10KΩ 10000 12KΩ 12000 15KΩ 15000 22KΩ 22000 33KΩ 33000 47KΩ 47000 Potted Diode Module 5A K859901990A 5A Supervisory Diode Module Reset Keyways 5 Pack K859902467A CP BG and CP PB stations 6 Vdc LED Replacement Module Kit LED ser resistor modules K859902472A 06 CP BG and CP PB LED st...

Page 24: ...ig com signaling fedsig com Part Description Federal Signal Part Use Faceplate Label EN54 11 K71400701A CP BG x x x xxx xx 2 EN54 11 stations Faceplate Label Stainless Steel FIRE K71400976A 01 CP BG and CP PB stations Non EN54 11 EVAC 02 Non EN54 11 BIOHAZARD ALARM 03 Non EN54 11 GAS ALARM 04 Non EN54 11 Actuation Label White K71400699A 01 CP BG and CP PB red blue green and black stations Black 02...