Troubleshooting

Description and Specifications Manual

Troubleshooting

NOTE

: It is normal for the 46 Vdc output of the transformer to have 20-30 Vrms of AC 

ripple without load. With load the AC ripple significantly decreases.
If the 46 Vdc output of the transformer is about half of 46 Vdc, typical cause is a 

defective Diode Rectifier or Transformer. Lightning or a power surge may have damaged 

the Diode Rectifier or Transformer.
1.  Turn off AC power to the transformer. Verify AC power has been turned off.
2.  Disconnect wires X1 and X3 from the Diode Rectifier and carefully protect the 

wires from shorting.

3.  Connect voltmeter to X1 and X3. Turn on AC power and measure X1 and X3. 

Should measure about 100 Vac.

4.  Turn off AC power to the transformer. Verify AC power has been turned off.
5.  Connect voltmeter to X1 and X2. Turn on AC power and measure X1 and X2. 

Should measure about 50 Vac.

6.  Turn off AC power to the transformer. Verify AC power has been turned off.
7.  Connect voltmeter to X3 and X2. Turn on AC power and measure X3 and X2. 

Should measure about 50 Vac.

If the voltages above are incorrect, the entire transformer part number Q120246F-AL, 

will need to be replaced.
If the voltages above are correct, the Diode Rectifier part number Q115336A, will need to 

be replaced.

Getting Service

If you are experiencing any difficulties, contact Federal Signal Customer Care at:  

800-548-7229 or 708-534-3400 extension 7511 or Technical Support at: 800-524-3021 

or 708-534-3400 extension 7329 or through e-mail at: [email protected]. For 

instruction manuals and information on related products, visit: http://www.fedsig.com/

Summary of Contents for 2001TRBP

Page 1: ...Description and Specifications Manual 2561831 Rev B2 1018 Printed in U S A Copyright 2013 2018 Federal Signal Corporation Models 2001TRBP 2001TRBP 480 and 2001TRBP KIT Transformer Rectifier ...

Page 2: ...y is in lieu of all other warranties express or implied contractual or statutory including but not limited to the warranty of merchantability warranty of fitness for a particular purpose and any warranty against failure of its essential purpose 2645 Federal Signal Drive University Park Illinois 60484 3167 www fedsig com Customer Support 800 548 7229 1 708 534 3400 Technical Support 800 524 3021 1 ...

Page 3: ...ng Service 11 Tables Table 1 Electrical Requirements for the Transformer Rectifier 7 Table 2 Contactors 7 Table 3 Environmental 7 Table 4 Physical 7 Table 5 2001TRBP Kit Contents 8 Table 6 2001TRBP and 2001TRBP 480 Contents 8 Figures Figure 1 Models 2001TRBP and 2001TRBP 480 Transformer Rectifier 6 Figure 2 Schematic Diagram 2001TRBP 9 Figure 3 Schematic Diagram 2001TRBP 480 10 Figure 4 Transforme...

Page 4: ...e FEMA REP 10 Nuclear Plant Guideline Planning If suitable warning equipment is not selected the installation site for the siren is not selected properly or the siren is not installed properly it may not produce the intended optimum audible warning Follow Federal Emergency Management Agency FEMA recommendations If sirens are not activated in a timely manner when an emergency condition exists they ...

Page 5: ...near the sirens Sirens may be operated from remote control points Whenever possible disconnect all siren power including batteries before working near the siren After installation or service test the siren system to confirm that it is operating properly Test the system regularly to confirm that it will be operational in an emergency If future service personnel do not have these warnings and all ot...

Page 6: ...ren control board heaters and chargers if battery equipped The 2001TRBP and 2001TRBP 480 includes a transfer relay contactor kit which allows primary operation from AC and battery backup when AC fails The transfer relay kit includes 48 Vdc contactor buss bars snubber and screws for attaching contactor to back plate inside Federal Signal Control Cabinet Figure 1 Models 2001TRBP and 2001TRBP 480 Tra...

Page 7: ...ecifications Table 1 Electrical Requirements for the Transformer Rectifier 2001TRBP 2001TRBP 480 Input Voltage 208 220 240 Vac 10 50 60 Hz single phase 416 440 480 Vac 10 50 60 Hz single phase Input Current 32 30 27 A 16 15 13 6 A Output Voltage 115 Vac at 10 A 46 Vdc at 130 A 115 Vac at 10 A 46 Vdc at 130 A Input Fusing 40 A slow blow max 40 A Slow blow max Continuous Full Output 30 minutes Table...

Page 8: ...s Description 2001TRBP includes 2001TRBP Service Part Number 2001TRBP 480 includes Transformer rectifier 120246F AL Q120246F AL 120868A 48 Vdc Contactor 131A182C Q131A182C 131A182C Fused wire 1461132A 1461132A Snubber 20000216 20000216 Pan Head screw 2 7011A069 08 7011A069 08 Brass washer 70700520 70700520 2 position buss bar 8402109A 8402109A Buss bar rt angle 8402138A 8402138A Diode Rectifier 11...

Page 9: ...port the transformer Electrical Connections Install the siren electrical system in compliance with local electrical codes and NEC recommendations Federal Signal also recommends that all user installed conduit connections enter from the bottom of the cabinet Disconnect all power and read all warnings at the beginning of this manual and before making connections Figure 2 Schematic Diagram 2001TRBP 2...

Page 10: ...Rectifier Figure 3 Schematic Diagram 2001TRBP 480 BLK RED POWER SOURCE FUSED H1 480 VAC H4 H3 440 VAC H2 416 VAC X1 100 VAC 50 VAC T1 X3 X2 46 VDC X5 X4 115 VAC Figure 4 Transformer Rectifier Wiring to Control Cabinet 5 4 2 1 3 10 10 F1F2 A A 2001TRBP and 2001TRBP 480 ...

Page 11: ... Vac 4 Turn off AC power to the transformer Verify AC power has been turned off 5 Connect voltmeter to X1 and X2 Turn on AC power and measure X1 and X2 Should measure about 50 Vac 6 Turn off AC power to the transformer Verify AC power has been turned off 7 Connect voltmeter to X3 and X2 Turn on AC power and measure X3 and X2 Should measure about 50 Vac If the voltages above are incorrect the entir...

Page 12: ...2645 Federal Signal Drive University Park Illinois 60484 3167 www fedsig com Customer Support 800 548 7229 1 708 534 3400 Technical Support 800 524 3021 1 708 534 3400 ...

Reviews: