12
3. Install conduit between the disconnect switch and the electrical power source. If the siren is installed
on a utility pole, add an entrance cap to the end of the conduit, as shown in figure 3-2.
4. Route two wires of the proper size from T1 and T2 in the RC2W, through the conduit to the siren
motor leads.
5. Route two wires of the proper size from L1 and L2 through the conduit to the power disconnect
switch.
6. Route two wires, of the proper size, from the disconnect switch to the power source.
7. Connect the FC to terminals L1 and 3 in the motor starter. See figure 3-4.
8. Replace the housing on the siren.
9. As a safety precaution to protect both personnel and equipment, it is highly recommended that the
siren and all control devices be solidly connected to an earth ground. If the siren is installed on a building,
ground the system to a metallic object known to be grounded. For pole mounted installations, drive a metal
rod or bar at least two feet (61 cm) into the ground, or as close as practical to the base of the pole. For
maximum protection, use a separate, continuous 10AWG or larger, wire from the siren frame to ground and
the cabinet of each control device to ground.
3-4.
PREOPERATION CHECKS
After the siren has been completely installed, perform the following checks before putting the siren into
service.
WARNING
The output level of a siren is capable of causing severe hearing discomfort or permanent
hearing damage. Therefore, ALWAYS wear hearing protection when performing tests or
maintenance on the siren.
A. Make sure that all air intakes and sound outlets are not obstructed.
B. For local test activation refer to the FC control installation manual no. 255294.
C. Check the operation of the control circuitry by initiating one or more signals from the FC control.
After the installation is complete and it has been established that the siren is operating properly, Federal
recommends that all control devices be padlocked to discourage tampering and vandalism.