background image

4

SUPPLY

AIR

SERVICE 

PLATFORM

CEILING 

JOISTS

AIR HANDLER SUPPORTS

(FIELD SUPPLIED)

AUXILIARY DRAIN PAN

(FIELD FABRICATED)

P-TRAP

PRIMARY 

DRAIN LINE

RETURN AIR

AUXILIARY 

DRAIN LINE

Horizontal Installation

Horizontal Application

This type of position is usually used in an attic or crawl space. The air
handler may be laid on the left or right side for horizontal applications.
The factory-installed coil is intended for left-side-down installation.

This type of installation requires a return air duct to be attached to the
air handler inlet. The opposite end of the return air duct is then routed
to a return air grille mounted to the ceiling or wall. This duct MUST be
no smaller than the inlet opening of the air handler.

For Horizontal Right Application:

1. Remove front panels from the air handler.

2. Remove coil assembly from the air handler.

3. Remove horizontal drain pan from left hand side of air handler and

re-install on right hand side. Change splash baffle location from left
hand to right hand side of drain pan flange.

4. Remove the horizontal coil support bracket from the right hand side

of the air handler.

5. Reinstall coil assembly in the air handler.

6. Reattach coil support bracket to the left hand side of the air

handler.

7. Replace front panels.

CAUTION

Horizontal applications in unconditioned areas, such
as attics above a ceiling, require special
precautionary measures. An auxiliary drain pan
having at least two inches overall clearance around
the unit MUST be field-fabricated and installed as
shown below. 
The drain outlet and drain line for the auxiliary
drain pan need not be trapped but should be sloped
to a suitable drain.

CAUTION

For optimum condensate drainage performance in
horizontal installations, unit should be leveled
along the length and width. Failure to follow this
caution may result in product or property damage.

CAUTION

A P-type trap must be installed in the primary drain
line as shown in figure 3 below.

11

3

Summary of Contents for AFPB24B1

Page 1: ...ing 6 Factory and Field installed Expansion Valves 6 Ductwork 7 Return Air Ducting 7 Return Air Platform Height 7 LINE VOLTAGE CONNECTIONS 7 24 VOLT CONTROL SYSTEM 8 CONDENSATE PLUMBING 8 WIRING DIAGR...

Page 2: ...ion which if not avoided could result in death or serious injury CAUTION indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury CAUTION used without th...

Page 3: ...ndividuals specially trained and experienced in the installation of this type equipment and related system components Installation and service personnel are required by some locales to be licensed Per...

Page 4: ...E DUCT 600 FPM 24 MINIMUM RETURN GRILLE 500FPM RETURN PLATFORM LINED WITH 1 FIBERGLASS INSULATION REFER TO LOCAL CODES CLOSET AIR HANDLER Upflow Installation With Return Duct DISCHARGE DUCT 600 FPM 24...

Page 5: ...rom left hand side of air handler and re install on right hand side Change splash baffle location from left hand to right hand side of drain pan flange 4 Remove the horizontal coil support bracket fro...

Page 6: ...filter grille may be installed for closet applications If this method is not desirable cabinet extension kit No 65 1647 for A24 A30 and A36 or No 65 1649 for A42 A48 and A60 may be ordered The extens...

Page 7: ...BE TAKEN TO AVOID OVERHEATING THE TXV VALVE AND CAUSING DAMAGE TO THE INTERNAL COMPONENTS 3 Attach the bulb securely with the copper strap provided 4 Insulate the bulb thoroughly with a suitable insu...

Page 8: ...4 2 5 163 8 41 6 221 4 56 5 3 7 6 3 7 6 13 4 4 4 2 5 163 8 41 6 221 4 56 5 3 7 6 3 7 6 13 4 4 4 2 5 11 8 WARNING BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT POWER SUPPLY MUST BE TURNED OFF AT THE HOU...

Page 9: ...ING IMPROPER INSTALLATION OF THE ELECTRICAL WIRING OR THE HEAT ASSEMBLY MAY RESULT IN FIRE SERIOUS PERSONAL INJURY OR DEATH UNIT FLEXIBLE TUBING HOSE OR PIPE DRAIN CONNECTION A POSITIVE LIQUID SEAL IS...

Page 10: ...0 5 3 10 5 3 kW does not include motor watts Ampacities and over current protection based on largest air handler motor load Refer to specific name plate for exact ampacity and overcurrent protection s...

Page 11: ...1 4 3 5 8 13 1 4 15 48 1 8 19 1 8 21 26 22 16 3 8 22 1 4 AFPC48B1 2 1 4 3 5 8 13 1 4 15 48 1 8 19 1 8 21 26 22 16 3 8 22 1 4 AFPC60A1 2 1 4 3 5 8 13 1 4 15 48 1 8 19 1 8 21 26 22 16 3 8 22 1 4 AFPC60B...

Page 12: ...30 1840 1770 1590 LOW 20 kW 0 35 15 kW 0 35 1360 1350 1340 1185 1080 Air flow shown at the following conditions No heat elements in air handler Decrease CFM 1 for 5 kW 7 5 kW or 10 kW heat kits Decrea...

Page 13: ...ompartment remove the cover plate from the element housing Remove cover plate Remove air handler field wiring box and discard Remove two screws 11 14 11 15 5 Cut the wire tie holding the heater plug a...

Page 14: ...other than 230 multiply temperature rise by capacity correction factor Refer to CFM tables to determine Cfm at total external static pressure in system For correction of unit output multiply the corr...

Page 15: ...TATIONS Limited Warranty does not include allowances for labor or travel expense connected with the installation of parts so furnished in this Limited Warranty or for field repair or servicing of the...

Page 16: ...r the general appearance of the units at the time of publication and the manufacturer reserves the right to make changes in design and construction at any time without notice For replacement parts ple...

Reviews: