M A I N T E N A N C E M A N U A L
Limited Warranty:
FEBCO warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event of
such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge. This shall constitute the sole and exclusive remedy for breach of warranty, and
the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged
if this product does not work properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or
any other circumstances over which the Company has no control. This warranty shall be invalidated by any abuse, misuse, misapplication or improper installation of the product.
THIS WARRANTY IS IN
LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
Any implied warranties that
are imposed by law are limited in duration to one year.
Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above limitations
may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to determine your rights.
General
1. Detailed maintenance manuals are available from your local FEBCO
representitive.
2. Rinse all parts with clean water prior to reassembly.
3. DO NOT USE ANY PIPE DOPE, OIL, GREASE OR SOLVENT ON ANY
PARTS unless instructed to do so.
4. Do not force parts. Parts should fit together freely. Excess force may
cause damage and render the assembly inoperable.
5. Carefully inspect seals and seating surfaces for debris or damage.
6. After servicing, repressurize the assembly and test to ensure proper
operation.
Disassembling the Check Valve
1. Close the outlet shutoff valve, then close the inlet shutoff valve. Bleed
residual pressure from the assembly by opening the #4, #3, and # 2
test cocks in this sequence.
2. Remove the cover bolts/nuts and lift the cover from the body. The
springs are retained and the cover should be pushed away from the
body approximately
1
⁄
4
inch.
3. Inspect/clean debris from the disc and seat ring. Replace worn or
damaged parts as required.
4. Replace the cover, ensure the spring assembly is positioned in the pivot
socket. If necessary, apply FDA approved grease to the O-ring groove in
the body to keep the O-ring in position while installing the cover.
5. Install the bolts and nuts and tighten.
Test Procedure
FEBCO recommends the use of the appropriate test method presented in
the ASSE Series 5000 manual that is consistent with your local codes.
Troubleshooting for Double Check Assemblies
PROBLEM CAUSE
SOLUTION
1. Check valve leaking
a. Debris on seating surface
Disassemble and clean
b. Leaking shutoff valve.
Disassemble and clean
2. Low flows
a. Mainline check fouled
Disassemble and clean
passing through
b. Bypass line plugged
Disassemble and clean
Servicing Check Valve Assemblies
A Division of Watts Water Technologies, Inc.
USA: 4381 N. Brawley • Ste. 102 • Fresno, CA • 93722 • Tel. (559) 441-5300 • Fax: (559) 441-5301 • www.FEBCOonline.com
Canada: 5435 North Service Rd. • Burlington, ONT. • L7L 5H7 • Tel. (905) 332-4090 • Fax: (905) 332-7068 • www.FEBCOonline.ca
IS-F-850/856-DC/DCDA 0613
EDP# 980048
© FEBCO, 2007