MSR128LUS/MSR128LUV USERS MANUAL EM-7375 Rev.2
4.3.3
DETAIL INFORMATION (DISCRETE)
When ‘Discrete’ is selected in Common Information setting, the following details are selectable. Operation Function
is not available with discrete inputs.
Figure 4.3.3: Detail information (discrete).
Alarm Description
Short description for ON (1) and OFF (0) status can be specified. Max. 10 characters. DO NOT use characters used
to separate cells in CSV format (period, comma, space, tab, etc.).
Alarm Output
Mark ‘X’ to when you want to output the alarm trip at the 53U’s Do terminal.
Caution !
The 53U module’s local alarm setting has a priority over that on the MSR128LU. Setpoints, deadbands and alarm
output setting will be ignored if they are specified at the 53U module.
In order to output alarms from the MSR128LU at the 53U’s Do terminal, the discrete I/O setting for the 53U must be
set to ‘Undefined.’ Please refer to the 53U operation manual for more information.
Output contact logic (N.O. or N.C.) depends upon the 53U setting.
Alarm Delay
Once the discrete signal status is changed, the alarm is tripped only after the predefined time has elapsed in order
to avoid unwanted trips caused by noise interference. Enter the time in seconds.
Alarm Node & Channel
Specify the node number of the device and the channel number ‘1.’
Normal & Alarm Colors
Colors specified for normal and alarm conditions are used for the alarm indicators in the digital display area on the
Record view.
Use the color palette.
4.3.4
OTHER CONTROLS
• Apply:
Click this button to apply new settings without closing the dialog box.
• Cancel:
Click this button to close the dialog box without applying new settings.
• OK:
Click this button to apply new setting and close the dialog box.