301 2nd Ave. Waltham, MA  02451-1133 USA  TEL: (781) 487-0088 FAX: (781) 370-4132

Copyright 1998

Part Number: 9000-0405

All Rights Reserved

Version: 1.3

Published in the U.S.A.

FireVac

®

7200 SERIES

EMERGENCY VOICE/ALARM

FIRE ALARM CONTROL

INSTALLATION/OPERATING

ADDENDUM

Technical Manuals Online! - http://www.tech-man.com

Summary of Contents for FireVac 7200 Series

Page 1: ...88 FAX 781 370 4132 Copyright 1998 Part Number 9000 0405 All Rights Reserved Version 1 3 Published in the U S A FireVac 7200 SERIES EMERGENCY VOICE ALARM FIRE ALARM CONTROL INSTALLATION OPERATING ADDE...

Page 2: ...Technical Manuals Online http www tech man com...

Page 3: ...J Status Indicator Board SIB 10R or 10Y 12 1 7 Microphone and Telephone Handset 12 1 8 Cabinets 12 1 9 Basic System Amplifier 12 1 10 Peripheral Devices 12 1 10 1 Addressable Output Modules 12 1 10 2...

Page 4: ...arm System with Manually Controllable Process Monitoring 47 2 10 Notification Appliances 54 2 10 1 Speakers 54 2 10 2 Strobes 54 2 11 Two Way Telephone System Hardware 54 2 11 1 Warden Station 54 2 11...

Page 5: ...iction of some authority In some areas this may be a local fire department in other areas it may be a building inspector insurance firm etc Different authorities may have their own local requirements...

Page 6: ...he field wiring diagrams To reduce errors and help in servicing the system all conductors should be tagged or otherwise coded and logged at installation to identify circuit assignment and polarity If...

Page 7: ...arelessness and safety hazards such as smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical circuits children playing with matches or arson Audi...

Page 8: ...on Terminal Descriptions Furnishes descriptions of each major FireVac 7200 System component requiring installation and typical interequipment drawings Chapter 3 Power Up Testing Provides initial power...

Page 9: ...SECTION ONE OVERVIEW 9000 0405 7 of 61 Technical Manuals Online http www tech man com...

Page 10: ...8 of 61 9000 0405 Technical Manuals Online http www tech man com...

Page 11: ...ogram FCP 1 2 Configurations The FireVac 7200 system can be configured in the following basic individual or combined systems A selective signaling single or dual channel fire alarm system A fire alarm...

Page 12: ...rd Display Unit KDU System Backplane with modules Card cage for plug in modules with brackets for the command center Microphone and telephone handset if required ALARM SUPERVISORY TROUBLE SILENCE J2 W...

Page 13: ...ol Unit Single Channel CCU S provides system wide manual control of all the speaker circuits and alarm tones that are broadcast by these circuits One CCU S is required for each system that provides se...

Page 14: ...cket mounted below the card cage 1 8 Cabinets The FireVac7200 cabinets consist of a backbox cabinet doors and mounting plate for the 7200 Series units The doors are half size and two are required for...

Page 15: ...ional microphone in the Remote Command Center B Push to Talk Receiver Module PTT R The Push to Talk Receiver Module PTT R receives the preamplified signals from remote PTT Ds It is housed in the main...

Page 16: ...14 of 61 9000 0405 Technical Manuals Online http www tech man com...

Page 17: ...SECTION TWO INSTALLATION TERMINAL DESCRIPTIONS 9000 0405 15 of 61 Technical Manuals Online http www tech man com...

Page 18: ...W2 DISCONNECT TROUBLE ALARM W1 8 7 6 5 4 3 2 1 2 E A 6 0 C 8 4 5 SW1 7 9 B D F 1 3 J4 AEU TB1 J7 Audio Evacuation Unit AEU 16 of 61 9000 0405 Technical Manuals Online http www tech man com...

Page 19: ...DIU with its associated power supply meets this requirement Designation Description Comments FIELD WIRING CONNECTIONS TB1 1 Loop 1 Class B Style 4 positive power limited See Figure 2 1 TB1 2 Class A S...

Page 20: ...Supervised 7 8 2 3 4 6 5 1 AEU TERMINALS 2 1 7 6 5 3 4 8 AUDIO SYSTEM BACK PLANE TERMINAL STRIP TB2 TYPICAL AOM 2 MODULE CAN BE CONFIGURED AS A SPEAKER TELEPHONE OR AUXILIARY CIRCUIT 7 AMM 2 5 4 5 9 0...

Page 21: ...ALS Note Wiring from AEU terminals 2 and 3 to last M500X Module shall be as short as possible and run in rigid conduit 4 5 1 3 2 AOM 2 8 7 9 6 4 1 3 2 M500X 4 1 3 2 M500X 4 1 3 2 M500X 4 5 1 3 2 AOM 2...

Page 22: ...able remote telephone interface modules AOM 2 for a dual channel system without auxiliary tone AEU SLC connections are identical to those shown in Figures 2 4 through 2 6 1 2 3 4 5 6 7 8 1 2 3 4 J1 TB...

Page 23: ...tput positive internal power limited connects to FCI MB TB5 3 TB4 7 Amp 1 Activation Single Channel Ampl Output negative internal power limited connects to FCI MB TB2 4 TB4 8 Single Channel Ampl Outpu...

Page 24: ...4 5 6 7 8 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 J1 TB1 TB2 TB4 J3 J4 J5 J6 J7 J8 J11 J10 J2 P7 P4 TB3 P10 P3 P6 P8 MAIN IN POWER REG POWER N C 7 8 2 3 4 6 5 1 TO AEU FIELD MODULES AEU TERMINA...

Page 25: ...2 3 4 5 5 7 8 9 10 11 12 13 14 15 16 1 2 3 4 J1 TB1 TB2 TB4 J3 J4 J5 J6 J7 J8 J11 J10 J2 P7 P4 TB3 P10 P3 P6 P8 S5 S2 S1 RECORD BYPASS REMOTE MIC P5 P1 1 2 3 4 1 2 3 1 2 MASTER CMD OUT AUX POWER CMD1...

Page 26: ...ssing scheme For each module five 5 address points are used Example CCU S 0 Uses address points 0 4 SIM SS 5 Uses address points 5 9 The FCP assigns addresses in the following order CCU SIM SS SIM A S...

Page 27: ...ddresses 55 through 59 5 Up SIM Addresses 60 through 64 6 Down SIM Addresses 65 through 69 6 Up SIM Addresses 70 through 74 7 Down SIM Addresses 75 through 79 7 Up SIM Addresses 80 through 84 8 Down S...

Page 28: ...MOVE TO ON POSITION TO REACTIVATE A SILENCED ALARM TONE OR TO OVERRIDE A MANUALLY ACTIVATED AUXILIARY TONE LED ILLUMINATES TO CONFIRM ACTIVATION MOVE TO NORMAL POSITION TO DEACTIVATE A MANUALLY ACTIV...

Page 29: ...TO CONFIRM ACTIVATION MOVE TO NORMAL POSITION TO DEACTIVATE A MANUALLY ACTIVATED ALARM TONE LED EXTINGUISHES TO CONFIRM DEACTIVATION AUXILIARY TONE SWITCH MOVE TO ON POSITION TO ACTIVATE AUXILIARY TON...

Page 30: ...ON OFF AUTO ON OFF AUTO ON OFF AUTO Fig 2 12c Switch Input Module Aux SIM A SPEAKER SELECT SWITCH MOVE TO ON POSITION TO ACTIVATE ASSOCIATED SPEAKER CIRCUIT LED ILLUMINATES TO CONFIRM ACTIVATION MOVE...

Page 31: ...TED REMOTE TELEPHONE LED ILLUMINATES TO CONFIRM ACTIVATION FOR REMOTE TELEPHONE INSTRUCTIONS ON OFF PHONE PATCH COMMAND PHONE ACTIVE COMMAND PHONE ACTIVE LED ILLUMINATES TO CONFIRM OFF HOOK CONDITION...

Page 32: ...ot used TB4 1 2 Not used TB5 1 Amp 2 Activation Single Channel operation with aux tone TB5 2 Amp 2 Activation Single Channel operation without aux tone TB5 3 Amp 2 Activation Dual Channel operation TB...

Page 33: ...POLARITY SHOWN POWER LIMITED AMP NO 2 OUTPUT CONTROL INPUT FROM AUDIO SYSTEM BACK PLANE OR AAI MODULE ALARM POLARITY SHOWN POWER LIMITED OUT OUT IN IN FORM C TROUBLE CONTACTS 2A 30 VDC RESISTIVE FOR C...

Page 34: ...NO TONE AFTER MESSAGE ON TONE AFTER MESSAGE FACTORY DEFAULT SWITCHES 6 7 8 USED TO DETERMINE THE NUMBER OF TIMES THAT VOICE MESSAGE WILL REPEAT SWITCH 6 7 8 OFF OFF OFF TONE ONLY NO VOICE 3 4 6 ON OFF...

Page 35: ...CEWAY AS EITHER THE ALU OR AEU SLCs CONNECT SHIELDS TOGETHER AT ALL ELECTRICAL CONNECTION BOXES AND LEAVE THE CONNECTION FLOATING DO NOT CONNECT TO EARTH GROUND UNSHIELDED WIRE CAN BE USED IF FCI AAM...

Page 36: ...limited Connect to speakers AOMs and AAIs TB1 5 Class A field wiring power limited Connect to speakers AOMs and AAIs TB1 6 Class A field wiring power limited Connect to speakers AOMs and AAIs TB2 1 S...

Page 37: ...4 5 6 TB1 TB2 S1 J1 P1 BACK UP ON BACK UP SWITCH S1 MOVE TO ON POSITION NOTES SHIELDED CABLE IS RECOMMENDED TO REDUCE RFI EMI EMISSIONS AND INTERFERENCE IF FCI AAM 25 CIRCUIT IS RUN IN THE SAME CONDU...

Page 38: ...e main audio amplifier and a remote distributed amplifier The primary function of the AAI is to supervise and activate the distributed amplifier The AAI switches primary alarm tone and or recorded mes...

Page 39: ...wer limited to FCI MB TB2 3 TB2 2 Activation Negative power limited to FCI MB TB2 4 TB2 3 Amplifier Positive power limited to FCI MB TB1 1 TB2 4 Supervision Negative power limited to FCI MB TB1 3 Swit...

Page 40: ...WER REG POWER N C 1 2 3 4 1 2 5 9 8 7 6 4 0 1 2 3 5 9 8 7 6 4 0 1 2 3 AC LOSS RELAY TB2 BATTERY P2 P1 TB1 HOT NEU EARTH J1 GRND FAULT BATT TRBL AC ON 1 2 3 1 2 3 4 5 6 7 8 9 101112 1 2 3 4 TB1 TB2 P5...

Page 41: ...STER CMD OUT AUX POWER CMD1 IN TB6 TB2 TB5 MAIN IN POWER REG POWER N C 1 2 3 4 1 2 AC LOSS RELAY TB2 BATTERY P2 P1 TB1 HOT NEU EARTH J1 GRND FAULT BATT TRBL AC ON 1 2 3 1 2 3 4 1 2 3 4 5 6 TB1 TB2 S1...

Page 42: ...N SUPERVISED TRANSFORMER CONNECTION TRANSFORMER TO POWER SUPPLY BATTERY CHARGER CONNECTOR P1 BATTERY CONNECTION LEAD ACID BATTERIES ONLY MAX CHARGING RATE 0 8A 27 6 V MAX CHARGER CAPACITY 17 AH BATTER...

Page 43: ...tral TB1 5 Not used TB2 1 A C Power N C Normally Closed TB2 2 Failure N O Normally Open TB2 3 C Common Form C Dry Contact CONNECTORS P1 Header AC Transformer Cable Non Power Limited P2 Header Battery...

Page 44: ...TO ON AU TO ON 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 4 3 2 1 AU TO ON AU TO ON AU TO ON AU TO ON AU TO ON MA NU AL SE LE CT AL AR M TO NE AU X TO NE LA MP TE ST A LL CA LL CO MM AN D...

Page 45: ...ION TERMINAL 24 VDC FROM BACKPLANE AMPLIFIER ACTIVATION TERMINALS OUT OUT IN IN PTT R MICROPHONE RISER NOT USED Figure 2 24 Designation Description Comments TB1 1 Microphone Input positive power limit...

Page 46: ...CENTER BACK PLANE PTT DRIVER BOARD IN REMOTE COMMAND CENTER CABLE CONNECTION J12 TB1 TB2 J1 GRN BRN RED BLU BLK WHT GRN BRN BLU RED WHT BLK Figure 2 25 PTT Driver Backplane Connections RATINGS Voltag...

Page 47: ...H ONES DIGIT 5 9 8 7 6 4 0 1 23 5 9 8 7 6 4 0 1 2 3 CLASS A B OUT CLASS A B OUT CLASS A RETURN CLASS A RETURN SHIELD GROUND WIRE CONNECTION SHIELD GROUND WIRE CONNECTION NOT USED NOT USED IN OUT OUT I...

Page 48: ...4 6 5 1 7 AMM 2 5 4 5 9 0 6 8 3 2 1 9 8 7 6 4 0 1 2 3 RED 2 1 7 6 5 3 4 8 FROM AEU SLC MODULES TO AEU SLC MODULES TWISTED UNSHIELDED WIRE 40 OHMS MAX 0 5 uF MAX 18 MIN AEU SLC TERMINALS AUDIO SYSTEM...

Page 49: ...gure the audibles for silenceable operation and the strobes non silenceable 2 8 Fire Alarm System with Two Way Telephone Communication Figure 2 29 shows a typical riser for a fire alarm system with tw...

Page 50: ...STROBES THROUGHOUT BUILDING HORNS THROUGHOUT BUILDING SINGLE PAIR ALL OTHER CIRCUITS AMPLIFIER POWER FROM SPSU V NON RESETTABLE AOM 2 CONFIGURED AS SILENCEABLE DRY CONTACT GENERAL ALARM TB2 1 2 3 4 C...

Page 51: ...6 15 14 13 12 11 10 9 4 3 2 1 AUTO ON AUTO ON AUTO ON AUTO ON AUTO ON AUTO ON AUTO ON AUTO ON AUTO ON AUTO ON NORMAL CONNECT NORMAL CONNECT NORMAL CONNECT NORMAL CONNECT NORMAL CONNECT COMMAND PHONE P...

Page 52: ...SYSTEM RISER SEE NOTES AEU SLC TWISTED UNSHIELDED WIRING NOTES USE TWISTED SHIELDED WIRE FOR TELEPHONE CIRCUITS IF TELEPHONE CIRCUITS ARE RUN IN THE SAME CONDUIT OR RACEWAY AS EITHER THE ALU OR AEU S...

Page 53: ...AOM 2s AND WARDEN STATIONS OR PHONE JACKS AND TO TERMINATE CLASS B WIRING FROM BACK PLANE TO LAST AOM 2 DOTTED LINES SHOW OPTIONAL WIRING FOR CLASS A TYPE TELEPHONE RISER AND CLASS A TYPE CONNECTIONS...

Page 54: ...FF ON AUT O OFF ON AUT O 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 4 3 2 1 OFF ON AUT O OFF ON AUT O OFF ON AUT O OFF ON AUT O OFF ON AUT O OFF ON AUT O OFF ON AUT O OFF ON AUT O OFF ON A...

Page 55: ...NOTE USE TWISTED UNSHIELDED WIRE 40 OHMS 0 5 MICROFARADS MAX ASSIGN EACH AOM 2 A UNIQUE ADDRESS AOM 2 RELAY CONTACT RATINGS RESISTIVE 2 A 30 VDC INDUCTIVE 1 A 30 VDC 0 6 PF PILOT DUTY 0 6 A 30 VDC 0...

Page 56: ...nd telephone receptacles used in the two way telephone system 2 11 1 Warden Station A Warden Station consists of a telephone handset hookswitch assembly installed in a locked surface or flush cabinet...

Page 57: ...in Figure 2 37 Unless otherwise indicated on the unit all field wiring circuits are power limited except AC power circuit Standby battery circuit Municipal box auxiliary circuit BACK UP ON 8 7 6 5 4 3...

Page 58: ...rcuit types NOTE 5 Route all field wiring to maintain a minimum of 1 4 inch separation between power limited and non power limited circuit types Additional conduit connections may be made in the respe...

Page 59: ...SECTION THREE POWER UP TEST PROCEDURE 9000 0405 57 of 61 Technical Manuals Online http www tech man com...

Page 60: ...58 of 61 9000 0405 Technical Manuals Online http www tech man com...

Page 61: ...System must be configured using the Field Configuration Program Users can perform project specific programming via the FCP 7200 program Copies of the system configuration operation should be given to...

Page 62: ...four 4 times whenever an initiating device is actuated B Supervisory Tamper Test All supervisory tamper devices OS Y valve post indicator valve etc connected to the disconnected zones signaling line...

Page 63: ...ch on the alpha numeric display 4 Press the RESET LAMP TEST switch on the KDU L KDU to select the Fire Drill option notice the word Drill appears above this switch 5 Press the ACKNOWLEDGE switch for t...

Page 64: ...Technical Manuals Online http www tech man com...

Page 65: ...Technical Manuals Online http www tech man com...

Page 66: ...301 2nd Ave Waltham MA 02451 1133 USA TEL 781 487 0088 FAX 781 370 4132 Technical Manuals Online http www tech man com...