2.4 Basic System Amplifier
2.4.1 FCI-Motherboard (FCI-MB)
The FCI-MB microprocessor-based module controls and supervises the functions of the 25 VRMS amplifiers
in the FireVac
®
7200. This module is “DIP" switch programmed and can house 1 or 2 amplifiers, each capable
of supplying 25 Watts. These amplifiers (FCI-AAM-25) are activated either by hardwired input or, in the case
of a distributed amplification system, via the AAI unit. Recorded messages are held in EEPROM memory on the
FCI-MB.
FIELD WIRING
Designation
Description
Comments
TB1-1
TRBL N/C
Trouble dry contacts, normally closed, power limited
TB1-2
TRBL N/O
Trouble dry contacts, normally open, power limited
TB1-3
TRBL COM
Trouble dry contacts, common, power limited
TB2-1
Amp. 1 Activation ( - )*
TB2-2
Amp. 1 Activation ( +)*
TB2-3
Amp. 1 Activation (+)*
TB2-4
Amp. 1 Activation ( - )*
TB3-1, -2
Not used.
TB3-3
Amp. power
Power input ( - ), non-power limited. From Back plane TB4-1.
TB3-4
24 VDC (nom.)
Power input (+), non-power limited. From Back plane TB4-2.
TB3-5
Not used.
TB4-1, -2
Not used.
TB5-1
Amp. 2 Activation ( - )*
Single Channel operation with aux. tone
TB5-2
Amp. 2 Activation (+)*
Single Channel operation without aux. tone
TB5-3
Amp. 2 Activation (+)*
Dual Channel operation
TB5-4
Amp. 2 Activation ( - )*
Distributed Amplifier operation
TB6-1
Not used
SWITCHES
S1
8-pos.
S5
Amplifier programming switches, See Figures 2, 3.
CONNECTORS
P3
Header, Amp. 2
Additional 25-watt amplifier connection point.
P4
Header, Amp. 1
Primary 25-watt amplifier connection point.
P5
Header, AAI or PTT-R
Connection point for an AAI in a distributed amplifier,
or for the PTT-R in a main amplifier.
P6
Header, microphone
Connection point for the system paging microphone, power limited.
This header is jumped out on a Dual Channel System,
or with distributed amplifiers.
P7
Header, aux.
power supply
Connection point for the distributed amplifier power supply.
*See Figure 2-4 for Single Channel operation without Aux. tone.
*See Figure 2-5 for Single Channel operation with Aux. tone.
*See Figure 2-7 for Dual Channel operation.
*See Figure 2-20 for Distributed Amplifier operation.
Table 2-4 FCI-MB Field Wiring, Switches, Connectors
30 of 61
9000-0405
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for FireVac 7200 Series
Page 2: ...Technical Manuals Online http www tech man com...
Page 9: ...SECTION ONE OVERVIEW 9000 0405 7 of 61 Technical Manuals Online http www tech man com...
Page 10: ...8 of 61 9000 0405 Technical Manuals Online http www tech man com...
Page 16: ...14 of 61 9000 0405 Technical Manuals Online http www tech man com...
Page 60: ...58 of 61 9000 0405 Technical Manuals Online http www tech man com...
Page 64: ...Technical Manuals Online http www tech man com...
Page 65: ...Technical Manuals Online http www tech man com...