8.4.1.6 InPut ERRoR
diagnostics of the local control inputs
From the FAULTS panel (point 8.4.1), press numerical key
5
to access the panel for viewing the diagnostics
of the local control inputs. The diagnostic state of each item monitored is reported, as shown in the following
table. Press ESC to return to the panel FAULTS.
8.4.2
IMP. REAL tIME
|
Real-time line impedance
Panel for checking the impedance values measured in real time, and percentage variations from the value stored during start-up, using the “Line
impedance acquisition” procedure.
The lines being used are listed. You can select a numerical key to access the corresponding panel indicating
the impedance measured in Ohms referred to the parallel of lines A and B connected to that line.
8.4.1.7 CoMMunICAtIon FAuLt
diagnostics of the internal data communication of VAC 2006
From the FAULTS panel (point 8.4.1), press numerical key
6
and access the panel for viewing the diagnostics
of the internal data communication of VAC 2006. The diagnostic state of each item monitored is reported in
the following table. Press ESC to return to the panel FAULTS.
Label
data being diagnosed
display
Cause
Action required
I2C bus
Data communications between the CPU
and the keys and front-panel LEDs
All
Fault
Internal communication failure.
Contact the Service Centre.
SPI
Data communication between CPUs.
All
Fault
Internal communication failure.
Contact the Service Centre.
Tab. 8.4.1.7
Label
Part being diagnosed
display
Cause
Action required
No input
fault found
Input contacts
1 to 8
Empty
list
No failure, or monitoring not
enabled for any input contacts
-
Input in fault:
List
number of
inputs
Break or short circuit in the line
connecting the contact
Check integrity of the line connecting the balancing
resistors and the activation contact. If the problem
persists, disconnect the line connecting the
activation contact and connect a 20 k
W
resistor
between the +24V service terminals and the control
input. If the problem persists, contact Servicing.
Inputs fault
resumed:
Failure cleared due to previous
failure signal
Access the Report> FAULTS panel from the
OPERATOR menu and carry out a MANUAL
RESET of the FAILURE signal.
General Input
Fault:
Empty
list
Failure of the internal communi-
cation between the CPU and the
inputs controlled stage.
If the problem persists, contact Servicing.
General Fault
resumed:
Failure cleared due to previous
failure signal
Access the Report> FAULTS panel from the
OPERATOR menu and carry out a MANUAL
RESET of the FAILURE signal.
Tab. 8.4.1.6
If the percentage of variation exceeds the level of tolerance set at the time of configuring the system, a “LOUDSPk LINE FAULT” due to an
excessively high or low impedance (Impedance Hi or Impedance Low) will be signalled.
Press ESC to return to the INSPECTION panel.