System Manual | 2013
VAIE 2000 | Voice Alarm Integrated Systems
VAC 2006 • VAR 2006
UK
8.4.1
FAuLtS
For viewing the failed components
Six groups are listed, with a generic indication of the fault condition.
The categories of failed parts and generic signalling of their states are shown in the
table below.
Press the associated numerical key (
1-6
) to select the sub-panel and view the details
of the failure, as illustrated under points below
or
Press ESC to return to the INSPECTION panel.
8.4.1.1 Automatic resetting of the acoustic signal (beep) following clearing of a failure
If the cause of a failure is cleared before the beep is reset manually (see OPERATOR Menu, point 8.5.3.1, page 105), the VAC 2006 will reset
the beep automatically, extinguish the FAULT LED and indicate RES (RESUMED) in the label of the part that had FAILED. The RESOLVED
signal will be stored until a MANUAL RESET of the failure signal is carried out from the FAULTS panel via the OPERATOR menu.
Tab. 8.4.1.1
Label
diagnostic category
See panel
Signalling Cause
1-Loudspk Line
Loudspeaker lines
LOUDSPk. LINE FAULT
ALL
Ok
No faults
2-Voice Alarms
Emergency sources
VOICE ALARMS FAULT
3-Amplifiers
Power amplifiers
Ground fault loudspeaker lines
AMPLIFIER FAULTS
4-Power Supply
Primary and secondary power supplies
Management memory display
POWER SUPPLY FAULTS
FAULT
At least 1 fault detected
and on-going
5-Control Input
Local input contacts
CONTROL INPUT FAULT
RES
At least 1 fault cleared
and no on-going faults
6-Communication VAC 2006 internal data communication COMMUNICATION FAULT