STARTING AND REGULATION
071011_2_A
GAS XP60/2CE EVO
14
CALIBRATION OF THE AIR PRESSURE SWITCH (PA)
The air pressure switch checks the minimum AIR pressure of the fan.
CALIBRATION OF THE MINIMUM GAS PRESSURE SWITCH (PGMIN)
N.B. The help of a combustion analyser will be necessary for the setting.
The air pressure switch checks the minimum AIR pressure
of the fan. When the air pressure value generated by the
fan is lower than the value set to the air pressure switch,
the burner goes to lockout.
For the setting it is necessary the support of a combustion
analyser: then proceed like follows:
A) Obstruct the air inlet gradually without changing the
position of the shutter, until you obtain a defect of air: CO
<= 10.000 ppm.
B) Turn the regulation collar of the pressure switch slowly
until you obtain the safety lock-out of the burner.
C) Open completely the air inlet and start the burner.
D) Repeat point-A) and control the "intervention" of the
air pressure switch.
Fig. 10
1-Cover screw 2-Regulation collar 3-Regulation indicator
It is connected in series with the thermostats of the boiler
and it stops the burner when the gas pressure is less then
the value of the set point (set the value 20% inferior of the
operation gas pressure). The minimum gas pressure
switch is mounted on the gas train in correspondence of
the valve VS. For setting it proceed as follows:
A) Bring the burner to the maximum power setted
(relative to the heat generator).
B) Measure the pressure on the outlet of the pressure
switch and close slowly the manual gas valve until the
pressure is 20% less than the measured pressure.
C) Turn slowly the regulation collar of the pressure switch,
until the lock-out of the burner is obtained.
D) Open the manual gas valve completely and start the
burner.
E) Repeat point A) and control the intervention of the
pressure switch.
Fig. 11
1-Cover
screw
2-Regulation
collar
3-Regulation
indicator
4-Pressure
control
connection
of
the
pressure
switch
GB
Summary of Contents for GAS XP60/2CE EVO
Page 66: ...071011_5_A GAS XP60 2CE EVO 5 1 2 2 2 2 3 2 1 3 2 2 1 3 1 2 RUS...
Page 67: ...071011_5_A GAS XP60 2CE EVO 6 Fig 3 GAS XP60 2CE EVO RUS...
Page 72: ...071011_5_A GAS XP60 2CE EVO 11 GAS XP60 RUS...
Page 73: ...071011_5_A GAS XP60 2CE EVO 12 Fig 7 WARNING RUS...
Page 81: ...071011_5_A GAS XP60 2CE EVO 20 1 1 2 2 3 3 4 4 5 5 6 6 7 7 1 1 2 2 3 3 1 1 2 2 3 3 4 4 5 5...
Page 82: ...071011_5_A GAS XP60 2CE EVO 21 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 1 1 2 2 3 4 4 4 1 1 1 1 2 2 3 3...
Page 83: ...071011_5_A GAS XP60 2CE EVO 22 p 1 1 2 2 3 3 4 4 5 5 6 6 7 7 2 1 2 1 2 IV 2 2 3 3...