Troubleshooting
Code (hexadecimal) Message
Conditions
Procedure
FFF4
IO-Link device model
QDPHLVGLႇHUHQW
This occurs when the model name
LQGH[QXPEHU>SURGXFWQDPH@
character string) of the registered IO-
/LQNGHYLFHGLႇHUVIURPWKHPRGHO
name of the device that is actually
connected, when device validation
VHWWLQJYDOXHQXPEHU0LVVHWWR
³7\SHQDPH´&\FOLFFRPPXQLFDWLRQ
is not performed with the applicable
IO-Link device.
Change the setting value for device
YDOLGDWLRQVHWWLQJYDOXHQXPEHU
M30) to a value other than “Type
QDPH´
Or, connect the correct IO-Link
device.
)))
Unsupported setting
value version
The version of the setting value data
restored to setting value memory is
new, and it may not be possible to
recognize some of it.
8SGDWHWKH¿UPZDUHRIWKLVSURGXFW
)))
Internal temperature
is too high
This occurs when the temperature
RIWKHPDLQ&38H[FHHGV&7KH
error occurs every 10 minutes.
Lower the operating temperature
of this product, install a cooling fan,
RUORZHUWKHRXWSXWORDGFXUUHQWIRU
example, by using a separate relay).
FFF7
EEPROM write
frequency is too high
The setting value write count occurs
under the following conditions.
•
The count is cleared if nothing is
ZULWWHQIRUVHFRQGV
•
When writing twice with a frequency
of once in less than 1 second.
•
When writing 20 times with a
frequency of 1 in less than 10
seconds.
•
When writing 200 times with a
frequency of once in less than 110
seconds.
&RQ¿UPZKHWKHUVHWWLQJYDOXHZULWH
operations are being performed
frequently from the host PLC.
&RQ¿UPZKHWKHU,2/LQNGHYLFH
parameters are frequently rewritten,
with automatic device parameter
EDFNXSVHWWLQJYDOXHQXPEHU0
VHWWR³%DFNXS´RU³%RWK´
FFF8
Software version
does not match
There is version incompatibility with
WKHPDLQ¿UPZDUH¿HOGQHWZRUN
FRPPXQLFDWLRQ¿UPZDUHRU,2/LQN
communication logic, and some
functions may not operate normally.
Update the FPGA data of this product
DQGWKHQHWZRUNFKLS¿UPZDUH
FFF9
Network chip is not
operating
This occurs when there is no
communication between the main
CPU and the chip that is performing
¿HOGQHWZRUNSURFHVVLQJ
The network chip may have failed, or
power may have turned OFF while
WKHQHWZRUNFKLS¿UPZDUHZDVEHLQJ
updated.
FFFA
Network
communication has
stopped
7KLVRFFXUVZKHQ¿HOGQHWZRUN
communication is established but
then disconnected. The error will be
automatically cleared when the status
is restored.
Check whether the Ethernet cable is
disconnected, the host PLC has been
reset, or the power has turned OFF.
&RQ¿UPWKHKRVW3/&SDUDPHWHUV
This product may stop being
recognized on the network if host
PLC network settings are changed.