Heat recovery unit with cooling circuit - 

RCF

 -

0208-6180549-rev. 02

8

GB

Controls manual 

Heating LED 
 

• 

ON if the unit is in  

 

Heating mode. 

 

Cooling LED 
 

• 

ON if the controller  

 

is in Cooling mode

If  neither  the  HEAT  LED  or  the 
COOL  LED  are  lit,  the  controller  is  in 
STANDBY mode.

On board control panel

The  control  panel  on  borad  of  the  unit 
performs the same functions and displays 
the  same  parameters  of  the  remote 
panel.
The  setting  procedure  are  the  same 
described for the remote panel. 
The “Upwards arrow” button operates also 
as “Mode” button, while the “Downwards 
arrow” button operates also as “Set” but-
ton.

Parameter programming – Menu levels

The  setting  parameters  of  the  control 
device may be modified through the con-
trol panel keyborad. The various parame-
ters  are  organized  in  groups  accessible 
when  pressing  the “mode”  and “on-off” 
buttons  at  the  same  time.  Each  menu 
level  is  identified  by  a  mnemonic  code 
which  appears  on  the  display.  For  more 
info please refer to the following page.

Buttons

 

 

Selects the operating mode:
If  the  Heating  mode  is  enabled,  each  time 
the button is pressed the following sequence 
occurs:
stand-by ->� cooling ->�heating -> stand-by
If the Heating mode is not enabled: 
stand-by -> cooling -> stand-by
 

 

 

Resets alarms and modifies the set point.
Press  once  to  reset  all  inactive  alarms  that 
can be reset manually.
If you hold the button down for 2 seconds, 
the  unit  displays  the  set  point  of  the  set 
mode. 

 

       

If  you  press  both  buttons  at  the  same  time 
and then release them within 2 seconds, you 
go down one level in the display menu.
If  you  press  both  buttons  for  more  than  2 
seconds, you move one level up. 
If the last level of a menu is displayed, press 
the button and release it within two seconds 
to go up one level.

In  menù  operating  mode  it  shows  the  pre-
vious  label  or  increases  the  shown  value 
(depending on the context). 

In  menù  operating  mode  it  shows  the  fol-
lowing  label  or  decreases  the  shown  value 
(depending on the context)

MODE

SET

Display

In Normal mode, the unit displays:
•  the  control  temperature,  in  tenths  of 
degrees  Celsius  with  a  decimal  point  or 
in Fahrenheit with no decimal point.
•  the  alarm  code,  if  at  least  one  is  acti-
ve.  If  several  alarms  are  active,  the  unit 
displays  the  first  alarm  listed  in  the 
Alarm Table. 
•  If  temperature  control  is  not  based 
on  the  analogue  inputs  and  is  linked  to 
the  status  of  a  digital  input  (AI1  or  AI2 
configured  as  digital  inputs),  the “On” 
or “Off”  label  will  be  displayed,  depen-
ding  on  whether  temperature  control  is 
active or not. 
•  In  Menu  mode,  displaying  varies 
according  it  the  position.    Special  labels 
and codes are used to help users identi-
fy the function that has been set.
Decimal point: when displaying the ope-
rating  hours,  it  indicates  that  the  value 
must be multiplied x 100.

In  normal  operation,  the  display  shows  
the temperature given by the NTC probe  
on the exhaust flow (room temperature).
To  display  the  setting  keep  the  button 
“set” pushed for nearly 3 seconds.
 

Leds

LED 1 compressor 1
 

• 

ON if compressor 1  

 

is active

 

• 

OFF if compressor 1  

 

is inactive

•    BLINK if safety timing is in progress

Defrost LED
 

• 

ON if defrosting is  

 

active

 

• 

OFF if defrosting     

 

is disabled or has been  

 

completed

•      BLINK  if  timing  is  in  progress  (defro-
sting time)

Electric heater LED
 

• 

ON if the internal    

 

anti-freeze electric heater  

 

are on

•  OFF  if  the  internal  anti-freeze  electric 
heater are off

MODE

SET

Summary of Contents for RCF Series

Page 1: ...0208 6180549 rev 02 FAST S p A CONTROLS MANUAL GB HEAT RECOVERY UNITS WITH COOLING CIRCUIT RCF SERIES...

Page 2: ......

Page 3: ...ristics 6 Installation of remote panel 6 Wiring of remote panel 7 User interface 7 Men levels 9 Components 10 Functions 11 Diagnostics 13 Parameters setting 16 Parameters 17 Technical characteristics...

Page 4: ...oys Seamless round copper tubes for air conditioning and refrigeration 2 designed manufactured and commercialized in compliance with the following EEC Directive PED safety 97 23 CE Machinery safety 98...

Page 5: ...ly limited through the use of technical protection means and measures G E N E R A L H A Z A R D S I G N A L Carefully adhere to all the indications n e x t t o t h e i c o n Failure to comply with the...

Page 6: ...assword inside the electrical panel remote panel max distance 150m to be connected directly to the unit wiring cable not included Troubleshooting The controls check and mark the fol lowing possible fa...

Page 7: ...onfigured as digi tal inputs with parameters Pa H05 Pa H06 Pa H08 8 digital inputs are therefore available Wiring of remote panel Important Never connect the keyboard when the instrument is on Avoid s...

Page 8: ...r more than 2 seconds you move one level up If the last level of a menu is displayed press the button and release it within two seconds to go up one level In men operating mode it shows the pre vious...

Page 9: ...D d I s r e t e m a r a P r A P d r o w s s a P s s P e u l a V g n i l o o C t e S e u l a V g n i t a e H t e S e u l a V t u p n I e u g o l a n A s u t a t S t u p n I l a t i g i D x e d n I r e...

Page 10: ...and start up of the same com pressor compressor on off safety time con trolled by parameter Pa C01 This parameter also applies to when the device is started up ON OFF Pa C01 Pa C02 Time COMPR Pa C01...

Page 11: ...cooling and freeheating are used to cool or heat the internal environment using outdoor air The external air enters the environment through a damper that mixes it with the recirculated air from insi d...

Page 12: ...e compressor is ON the control starts the defrost coun tdown 1 min countdown When 1 min pas sed the control device starts the defrosting process At this point Pad06 compressor valve time delay 30 sec...

Page 13: ...rms are sampled every 225 seconds Example if the number of events is set to 3 the duration of the alarm must last between 2 225 seconds and 3 225 seconds for the alarm to be switched from automatic to...

Page 14: ...OFF ON Automatically reset unless alarm events per hour reaches the value of parameter Pa A08 after which it is manually reset Not active when Pa A07 time is counted after a compressor is turned on E0...

Page 15: ...d as worn filters see digital inputs remains inactive for a period of time equal to Pa A05 Not active when the Pa A03 time is counted after fan is turned on OFF OFF3 Reset is carried out automatically...

Page 16: ...e contact is open The ID4 is configured as active when the contact is closed The ID5 input is configured as active when the contact is closed Relay 1 is connected to the compressor Relay 2 is connecte...

Page 17: ...ermal switch 2 Worn filters 3 Remote Heating Cooling 4 Remote ON OFF 5 Thermal switch compressor 2 6 Request for second compressor capa city step 7 damper opening Pa H22 Configuration of output NO2 0...

Page 18: ...a A01 Low pressure pressure switch by pass time Determines the delay between starting up the compressor and starting up the low pres sure digital alarm diagnostics It is expressed in seconds Pa A02 Nu...

Page 19: ...eating mode 3 continuous operating of fan in cooling mode on request in heating mode 4 continuous operating of fan in heating mode on request in cooling mode Pa P02 Delay between fan ON and com presso...

Page 20: ...if Pa H49 1 la temperatura al di sotto la quale viene avviato il ciclo di sbrinamento Pa d09 Temperature at which defrost ends if Pa H49 1 Temperature above which the defrost cycle is ended Pa d10 En...

Page 21: ...Enables dynamic set point 1 0 1 Flag 0 Pa H32 Dynamic set point off set in cooling mode 50 12 7 12 7 C 1 0 Pa H33 Dynamic set point off set in heating mode 0 12 7 12 7 C 1 0 Pa H34 Outdoor temperatur...

Page 22: ...Pa C02 ON ON safety time 36 0 255 Seconds 10 20 Pa C03 Temperature control hysteresis in cooling mode 15 0 25 5 C 2 Pa C04 Temperature control hysteresis in heating mode 15 0 25 5 C 1 5 Pa C05 Regula...

Page 23: ...eed in heating mode 100 0 100 80 Pa F17 Minimum fan speed temperature pressure set point in heating mode 100 500 800 C 10 kPa 10 180 Pa F18 Proportional band in heating mode 100 0 255 C 10 kPa 10 40 P...

Page 24: ...2 AWG 16 28 1 5 way p2 5 5 way connector with remote control and copy card programming AWG 24 30 1 2 3 way connector remote keyboard AWG 22 30 Display and LEDs 3 digits sign 5 red LEDs Buttons 2 butt...

Page 25: ...ntegrated In terms of automatic operating featu res as a type 1 action control device with reference to manufacturing tolerances and drifts As a class 2 device in relation to protec tion against elect...

Page 26: ...NOTES...

Page 27: ...ht to introduce at any time whatever modifications deemed necessary to the improvement of the product FAST S p A TRATTAMENTO DELL ARIA 35044 Montagnana PD Italy Via Luppia Alberi 170 Tel 39 0429 80631...

Reviews: