Controls manual 

Wiring of remote panel

During  the  connection  procedure 
between  the  electrical  panel  and  the 
remote  control  respect  the  following 
rules:
- do not apply to the analogue and digi-
tal  ouputs  powers  higher  than  the  ones 
declared in this manual;
-  make  the  connections  respecting  the 
wiring diagrams in this manual;
- keep the power  supply cables diveded 
from  the  control  cables  to  prevent  from 
interferences.

Analogue inputs

There are 4 analogue inputs: 
• 3 NTC temperature probes
•  1  input  which  may  be  configured  for 
an NTC probe or 4...20mA signal.
The  inputs  are  idetified  from  here  on  as  
AI1…AI4.

Digital inputs

There  are  5  voltage-free  digital  inputs 
identified from here on as ID1….ID15.
AI1,  AI2  and  AI4  may  also  be  added 
to  these  if  they  are  configured  as  digi-
tal  inputs  (with  parameters  Pa  H05,  Pa 
H06, Pa H08).
8 digital inputs are therefore available. 

Wiring of remote panel

Important!  Never  connect  the  keyboard 
when the instrument is on. Avoid short-
circuiting on the cables when the instru-
ment is on: this may damage the instru-
ment.

IA3 IA2 IA1

IA4

ID3 ID2 ID1

ID4

ID5

TC

12~ 12

12~ ALL GND GND

3

4

5

6

7

8

9

2

1

NO1 NO2

NO3 NO4

NO5 N

N

N

RELAYS 2(2)A 250V~

SERIAL

KEYB

P

X

E

IMG INFO

Layout view rear of the control panel on board on the unit

24: blue
25: red
26: black

26

25

24

2525

2424

2626

TERMINALE REMOTO

REMOTE TERMINAL

24 25 26

MORSETTIERA 

QUADRO ELETTRICO

ELECTRIC TERMINAL

BOARD

User interface

User interface

The user interface allows for the control 
of all the unit operations: 
• operating setting mode
• components checks and controls 
• alarms management 

Displays
The  device  shows  all  the  informations 
and  the  alarms  by  means  of  a  display 
and  led  signals  present  on  the  front 
panel.

n° 3 shielded cables not included 
(max. length 150 m;  min. section 
0.5 mm

2

)

Summary of Contents for RCF Series

Page 1: ...0208 6180549 rev 02 FAST S p A CONTROLS MANUAL GB HEAT RECOVERY UNITS WITH COOLING CIRCUIT RCF SERIES...

Page 2: ......

Page 3: ...ristics 6 Installation of remote panel 6 Wiring of remote panel 7 User interface 7 Men levels 9 Components 10 Functions 11 Diagnostics 13 Parameters setting 16 Parameters 17 Technical characteristics...

Page 4: ...oys Seamless round copper tubes for air conditioning and refrigeration 2 designed manufactured and commercialized in compliance with the following EEC Directive PED safety 97 23 CE Machinery safety 98...

Page 5: ...ly limited through the use of technical protection means and measures G E N E R A L H A Z A R D S I G N A L Carefully adhere to all the indications n e x t t o t h e i c o n Failure to comply with the...

Page 6: ...assword inside the electrical panel remote panel max distance 150m to be connected directly to the unit wiring cable not included Troubleshooting The controls check and mark the fol lowing possible fa...

Page 7: ...onfigured as digi tal inputs with parameters Pa H05 Pa H06 Pa H08 8 digital inputs are therefore available Wiring of remote panel Important Never connect the keyboard when the instrument is on Avoid s...

Page 8: ...r more than 2 seconds you move one level up If the last level of a menu is displayed press the button and release it within two seconds to go up one level In men operating mode it shows the pre vious...

Page 9: ...D d I s r e t e m a r a P r A P d r o w s s a P s s P e u l a V g n i l o o C t e S e u l a V g n i t a e H t e S e u l a V t u p n I e u g o l a n A s u t a t S t u p n I l a t i g i D x e d n I r e...

Page 10: ...and start up of the same com pressor compressor on off safety time con trolled by parameter Pa C01 This parameter also applies to when the device is started up ON OFF Pa C01 Pa C02 Time COMPR Pa C01...

Page 11: ...cooling and freeheating are used to cool or heat the internal environment using outdoor air The external air enters the environment through a damper that mixes it with the recirculated air from insi d...

Page 12: ...e compressor is ON the control starts the defrost coun tdown 1 min countdown When 1 min pas sed the control device starts the defrosting process At this point Pad06 compressor valve time delay 30 sec...

Page 13: ...rms are sampled every 225 seconds Example if the number of events is set to 3 the duration of the alarm must last between 2 225 seconds and 3 225 seconds for the alarm to be switched from automatic to...

Page 14: ...OFF ON Automatically reset unless alarm events per hour reaches the value of parameter Pa A08 after which it is manually reset Not active when Pa A07 time is counted after a compressor is turned on E0...

Page 15: ...d as worn filters see digital inputs remains inactive for a period of time equal to Pa A05 Not active when the Pa A03 time is counted after fan is turned on OFF OFF3 Reset is carried out automatically...

Page 16: ...e contact is open The ID4 is configured as active when the contact is closed The ID5 input is configured as active when the contact is closed Relay 1 is connected to the compressor Relay 2 is connecte...

Page 17: ...ermal switch 2 Worn filters 3 Remote Heating Cooling 4 Remote ON OFF 5 Thermal switch compressor 2 6 Request for second compressor capa city step 7 damper opening Pa H22 Configuration of output NO2 0...

Page 18: ...a A01 Low pressure pressure switch by pass time Determines the delay between starting up the compressor and starting up the low pres sure digital alarm diagnostics It is expressed in seconds Pa A02 Nu...

Page 19: ...eating mode 3 continuous operating of fan in cooling mode on request in heating mode 4 continuous operating of fan in heating mode on request in cooling mode Pa P02 Delay between fan ON and com presso...

Page 20: ...if Pa H49 1 la temperatura al di sotto la quale viene avviato il ciclo di sbrinamento Pa d09 Temperature at which defrost ends if Pa H49 1 Temperature above which the defrost cycle is ended Pa d10 En...

Page 21: ...Enables dynamic set point 1 0 1 Flag 0 Pa H32 Dynamic set point off set in cooling mode 50 12 7 12 7 C 1 0 Pa H33 Dynamic set point off set in heating mode 0 12 7 12 7 C 1 0 Pa H34 Outdoor temperatur...

Page 22: ...Pa C02 ON ON safety time 36 0 255 Seconds 10 20 Pa C03 Temperature control hysteresis in cooling mode 15 0 25 5 C 2 Pa C04 Temperature control hysteresis in heating mode 15 0 25 5 C 1 5 Pa C05 Regula...

Page 23: ...eed in heating mode 100 0 100 80 Pa F17 Minimum fan speed temperature pressure set point in heating mode 100 500 800 C 10 kPa 10 180 Pa F18 Proportional band in heating mode 100 0 255 C 10 kPa 10 40 P...

Page 24: ...2 AWG 16 28 1 5 way p2 5 5 way connector with remote control and copy card programming AWG 24 30 1 2 3 way connector remote keyboard AWG 22 30 Display and LEDs 3 digits sign 5 red LEDs Buttons 2 butt...

Page 25: ...ntegrated In terms of automatic operating featu res as a type 1 action control device with reference to manufacturing tolerances and drifts As a class 2 device in relation to protec tion against elect...

Page 26: ...NOTES...

Page 27: ...ht to introduce at any time whatever modifications deemed necessary to the improvement of the product FAST S p A TRATTAMENTO DELL ARIA 35044 Montagnana PD Italy Via Luppia Alberi 170 Tel 39 0429 80631...

Reviews: