Heat recovery unit with cooling circuit -
RCF
-
0208-6180549-rev. 02
7
GB
Controls manual
Wiring of remote panel
During the connection procedure
between the electrical panel and the
remote control respect the following
rules:
- do not apply to the analogue and digi-
tal ouputs powers higher than the ones
declared in this manual;
- make the connections respecting the
wiring diagrams in this manual;
- keep the power supply cables diveded
from the control cables to prevent from
interferences.
Analogue inputs
There are 4 analogue inputs:
• 3 NTC temperature probes
• 1 input which may be configured for
an NTC probe or 4...20mA signal.
The inputs are idetified from here on as
AI1…AI4.
Digital inputs
There are 5 voltage-free digital inputs
identified from here on as ID1….ID15.
AI1, AI2 and AI4 may also be added
to these if they are configured as digi-
tal inputs (with parameters Pa H05, Pa
H06, Pa H08).
8 digital inputs are therefore available.
Wiring of remote panel
Important! Never connect the keyboard
when the instrument is on. Avoid short-
circuiting on the cables when the instru-
ment is on: this may damage the instru-
ment.
IA3 IA2 IA1
IA4
ID3 ID2 ID1
ID4
ID5
TC
12~ 12
12~ ALL GND GND
3
4
5
6
7
8
9
2
1
NO1 NO2
NO3 NO4
NO5 N
N
N
RELAYS 2(2)A 250V~
SERIAL
KEYB
P
X
E
IMG INFO
Layout view rear of the control panel on board on the unit
24: blue
25: red
26: black
26
25
24
2525
2424
2626
TERMINALE REMOTO
REMOTE TERMINAL
24 25 26
MORSETTIERA
QUADRO ELETTRICO
ELECTRIC TERMINAL
BOARD
User interface
User interface
The user interface allows for the control
of all the unit operations:
• operating setting mode
• components checks and controls
• alarms management
Displays
The device shows all the informations
and the alarms by means of a display
and led signals present on the front
panel.
n° 3 shielded cables not included
(max. length 150 m; min. section
0.5 mm
2
)