background image

5

P/N 315-049708FA-4

punch (2) 1¼” (32mm) holes for input sampling and outlet
tubes, using the template as a guide. Clean all holes.

Sampling Tube  Installation

The 8741, 8742 and 8743 duct smoke detectors use a
specially notched sampling tube, which may be ordered
separately in one of four standard lengths.

ST-10

For duct widths of 6" to 1.0’

ST-25

For duct widths of 1.0’ to 3.0’

ST-50

For duct widths of 3.0’ to 5.0’ (requires support)

ST-100*

For duct widths of 5.0’ to 10.0’ (requires support)

*

This model is supplied as two 5 ft. sections with a coupling.
Assembly is required for installation.

Each model is manufactured with a different number and

size of sampling holes. Only the specific tube must be used

for the specified duct width.

Standard sampling tubes are steel tubes with air intake holes
drilled the entire length of the tube. These tubes can be cut
to length and must span at least 80% the width of the duct.
Sampling tubes over 3.0’ must be supported on the opposite
side of the duct. To ensure the correct operation, the red
stopper (stopper in installation kit) must be inserted in the
end of the air input sampling tube. If the input tube protrudes
through the opposite side of the duct, the opening around
the tube must be sealed. For custom duct widths, always
use the next longest standard size and cut down to the exact
requirement.

Once the airflow direction has been determined (refer to Figure
3), insert the input and outlet tubes into the duct housing.

INPUT TUBE HOLES

FACE AIR FLOW

INSERT RED STOPPER

THIS END OF INPUT TUBE

OUTLET TUBE INSTALLED
DOWNSTREAM OF AIRFLOW
DO NOT INSERT RED STOPPER

AIR FLOW DIRECTION

DUCT WIDTH

TUBE SUPPORT ONLY FOR DUCTS GREATER THAN 3 FEET WIDE

NOTE: Mountings shown
are typical. Detectors can
be installed side, bottom
or top of duct as long as
proper tube operation and
flow/pressure performance
is maintained.

Figure 3

Sampling Tube  Orientation

Summary of Contents for 8742

Page 1: ...c see char har har har harts on the page ts on the page ts on the page ts on the page ts on the page 1 1 1 1 12 of this manual 2 of this manual 2 of this manual 2 of this manual 2 of this manual TECHN...

Page 2: ...detector is equipped with cover removal switch SW1 that instantly provides a trouble condition upon removal of the clear cover For all testing and inspection with the cover removed the cover removal...

Page 3: ...R PLENUM FRESH AIR INTAKE DAMPER D D Figure 1 Typical Mounting of Duct Housing OUTLET TUBE INPUT SAMPLING TUBE CENTER LINE OF DUCT C L MOUNTINGTHE AIR DUCT HOUSING Location on Duct System This guideli...

Page 4: ...m of filters fires occurring in the filters will be detected but if the filters become blocked insufficient air flow through the duct unit will prevent the correct operation of the duct detector Duct...

Page 5: ...be cut to length and must span at least 80 the width of the duct Sampling tubes over 3 0 must be supported on the opposite side of the duct To ensure the correct operation the red stopper stopper in i...

Page 6: ...d the duct unit assembly in position and use 2 12 X 3 4 sheet metal screws packaged in the installation kit to secure the duct smoke detector to the HVAC duct sheet metal Air Duct Sampling Tube Pressu...

Page 7: ...e loop Note any limitations on the number of detectors and restrictions on the use of remote devices permitted for each circuit When replacing a detector with a different model be aware that existing...

Page 8: ...the initiating circuit 3 Do not use looped wire under base terminal 4 Break wire run to provide supervision of connection 5 The green grounding screw in the wiring compartment of the air duct housing...

Page 9: ...6 or 5 TB3 5 or 6 TB1 1A TB1 TB1 TB1 MODEL 8741 MODEL 8743 MODEL 8743 8710 8713 OPTIONAL REMOTE ALARM INDICATOR MODEL 8727C OR 8727W SEE NOTE 2 LOOP WIRES SEE COMPATIBLE CONTROL EQUIPMENT TABLE 8710 8...

Page 10: ...zle model AD TGN purchased separately available from Siemens Industry Inc insert the test gas nozzle into the hole in the red test plug in the unit cover Press can against cover for about 1 2 second t...

Page 11: ...F ed Farada arada arada arada araday S y S y S y S y Service R ervice R ervice R ervice R ervice Represent epresent epresent epresent epresentat at at at ati i i i ive ve ve ve ve If the fire alarm sy...

Page 12: ...P M 0 0 0 6 C P M 5 A F 0 5 8 4 3 0 5 1 3 N P 1 0 4 W L 3 A F 7 9 9 5 9 0 5 1 3 N P 1 0 4 W L A 4 E Z W L 4 A F 8 1 0 6 9 0 5 1 3 N P 1 0 4 W L A 8 E Z W L 3 A F 2 2 0 6 9 0 5 1 3 N P R O T C E T E D...

Reviews: