background image

15073 OWNER’S MANUAL 

447179 Issue 1 Rev. A 

 

45 

9.

9.   GLOSSARY

GLOSSARY  

Alarm Signal

.  A signal indicating an emergency requiring immediate action, such as an alarm for fire 

from a manual station, a waterflow alarm, or an automatic smoke detector. 

Alarm System

.  A combination of compatible initiating devices, control units, and notification appliances 

designed and installed to produce an alarm signal in the event of a fire. 

Audible Signal

. An audible signal is a sound made by one or more audible notification appliances, such 

as bells or horns, in response to the operation of an initiating device. 

Authority Having Jurisdiction (AHJ)

.  The organization, office, or individual responsible for approving 

equipment, installation or procedure. 

Class A Circuit

.  An initiating device or notification appliance circuit within which all components remain 

fully functional, even though a single open or ground exists in the circuit. 

Class B Circuit

.  An initiating device or notification appliance circuit within which some or all components 

may be disabled with a single open or ground exists in the circuit. 

End Of Line (EOL)

.  A device used to terminate a supervised circuit. 

General Alarm

.  A term usually applied to the simultaneous operation of all the notification appliances on 

a system. 

Ground Fault

.  A trouble condition in which a low resistance has been detected between the system 

wiring and conduit ground. 

Initiating Device Circuit (IDC)

. A circuit to which initiating devices are connected. 

Labeled

.  Equipment or materials to which have been attached a label, symbol, or other identifying mark 

of an organization acceptable to the authority having jurisdiction and concerned with product evaluation, 
that maintains periodic inspection of the production of such labeled equipment or materials.  And by 
whose labeling the manufacturer indicates compliance with appropriate standards or performance in a 
specified manner. 

Listed

.  Equipment or materials included in a list published by an organization acceptable to the authority 

having jurisdiction and concerned with product evaluation, that maintains periodic inspection of production 
of listed equipment or materials.  And whose listing states either that the equipment or material meets 
appropriate standards or has been tested and found suitable for use in a specified manner. 

NEC

.  National Electrical Code also published as NFPA standard 70. 

Notification Appliance

.  An electrically operated appliance used to indicate the system status such as a 

bell, horn, strobe light or speaker. 

Notification Appliance Circuit (NAC)

. A circuit to which notification appliances are connected. 

Power Supply

.  That portion of the fire alarm control unit, which provides the power needed to operate all 

control unit modules, as well as that, needed to operate all electrically powered initiating devices and all 
notification appliances. 

Trouble Signal

.  An audible signal indicating trouble of any nature, such as a circuit break or ground, 

occurring in the device or wiring associated with a fire alarm signal. 

Zone

.  A designated area of a building.  Commonly, zone, is interchanged with initiating device circuit.

firealarmresources.com

Summary of Contents for 15073

Page 1: ...et Tecumseh Michigan 49286 Phone 517 423 2111 Fax 517 423 2320 Copyright 2000 Faraday LLC All Rights Reserved P N 315 099082FA 2 RSE 300 REMOTE SIGNAL EXPANDER Owner s Manual 15073 P N 447179 Issue 1...

Page 2: ...21 4 2 DOOR HOLDER APPLICATIONS 27 5 PROGRAMMING 29 5 1 DIP SWITCH SETTINGS 29 5 1 1 Selecting the Input Output Configuration 30 5 1 2 Setting the Auxiliary Output 31 5 1 3 Setting the Input s Control...

Page 3: ...15073 OWNER S MANUAL 447179 Issue 1 Rev A ii This page is intentionally blank firealarmresources com...

Page 4: ...if local requirements dictate it Fire alarm control units cannot last forever Even though this control unit was made to last for the expected life of the Fire Alarm Systems any part could fail at any...

Page 5: ...ble contingency to be met in connection with installation operation and maintenance All specifications subject to change without notice Should further information be desired or should particular probl...

Page 6: ...should be used to install and maintain a functioning Fire Alarm Signaling System NFPA 70 1996 National Electrical Code NFPA 72 1999 National Fire Alarm Code NFPA 101 1997 Life Safety Code Other Stand...

Page 7: ...15073 OWNER S MANUAL 447179 Issue 1 Rev A vi This page is intentionally blank firealarmresources com...

Page 8: ...ion connection is intact The following situations will open the EOL supervision at the inputs indicating a trouble condition No or Low AC power No and Low battery condition Ground fault to the output...

Page 9: ...Supply output over current condition NAC output open shorted and over current condition Battery Charging and Supervision The 15073 provides a battery charging circuit for charging sealed lead acid bat...

Page 10: ...ate enclosure Input Circuits Two Input circuits For Power limited source Supervised Voltage Range 18 30VDC VFW Maximum Input Current 6 0 mA Notification Appliance Circuits Four Class B Style Y circuit...

Page 11: ...15073 OWNER S MANUAL 447179 Issue 1 Rev A 4 This page is intentionally blank firealarmresources com...

Page 12: ...gnal Expander 447179 Owners Manual 942667 Resistor 24K ohm 1 2 W 5 4 2 2 CONTROL UNIT MOUNTING The fire alarm control unit must be mounted in a properly accessible location as required by applicable c...

Page 13: ...er wiring installation may cause improper operation Avoid pulling one multi conductor cable for the entire system Instead separate high current input output from low current Wiring within the cabinet...

Page 14: ...ally Open contact 8 Common 2 5 A 30 VDC VAC resistive 9 Normally Closed contact 10 NAC 1 Output 24 VDC nominal 3 0A max Even though 11 NAC 1 Output each output is 12 NAC 2 Output 24 VDC nominal 3 0A m...

Page 15: ...e 15073 PC board This section also provides specific wiring details for accessories Consult your control unit manual for specific wiring information on the control unit being used If you are using a F...

Page 16: ...MANUAL 447179 Issue 1 Rev A 9 2 5 1 AC Wiring Figure 2 3 AC Wiring SUPERVISED NON POWER LIMITED 120 VAC 60Hz 2 5A MAX WARNING Note Branch current must be protected by a 15A overcurrent device firealar...

Page 17: ...wire to the negative side of battery 2 2 Connect jumper wire from the positive side of battery 2 to the negative side of battery 1 3 Connect red wire to the positive side of battery 1 Figure 2 4 Batte...

Page 18: ...ass B Supervised Input Circuits Figure 2 6 shows Style Y Class B supervised wiring from a fire alarm control unit to the 15073 board Use an EOL resistor as shown to enable notification input supervisi...

Page 19: ...ents When wiring to terminal 2 and 5 on TB2 you must use two separate wires Do not loop a single wire or twist two conductor wires together Do not use notification appliances on Style Z Class A circui...

Page 20: ...arm control unit This will cause a trouble on the fire alarm control unit when the 15073 opens its trouble contacts Note The N C contact is the relay contact that is closed when the 15073 has power an...

Page 21: ...15073 OWNER S MANUAL 447179 Issue 1 Rev A 14 This page is intentionally blank firealarmresources com...

Page 22: ...ire Alarm Control Unit FW 4000 12400 Fire Alarm Control Unit MPC 1500 12500 Fire Alarm Control Unit FW 200 13200 Fire Alarm Control Unit FW 400 13400 Fire Alarm Control Unit FWII FWII 2 15220 15240 A...

Page 23: ...Alarm Control Unit Figure 3 3 Connection to 12500 Fire Alarm Control Unit MON R R 2 2 1 1 1 1 2 2 3 3 4 4 IDC T B 2 A B C D E F T B 3 T B 5 NAC T B 6 T B 7 P7 9 10 11 6 4 3 1 Trouble Relay Input 2 In...

Page 24: ...NUAL 447179 Issue 1 Rev A 17 Figure 3 4 Connection to 13200 Fire Alarm Control Unit Figure 3 5 Connection to 13400 Fire Alarm Control Unit 1 3 2 6 7 8 9 4 5 11 10 12 1 3 2 6 7 8 9 4 5 11 10 12 fireala...

Page 25: ...trol Unit Figure 3 7 Connection to 16400 Fire Alarm Control Unit 6 7 8 9 2 1 3 Input 1 5 4 Input 2 12 Trouble Relay NAC 10 11 R 1 2 1 2 1 2 1 2 1 2 EOL 24K 1 2W 5 1 2 3 4 1 3 2 Input 1 EOL 10K 1 2W 5...

Page 26: ...it Figure 3 9 Connection to 16450 Fire Alarm Control Unit 6 7 8 9 EOL 10K 1 2W 5 3 Input 1 1 2 Input 2 4 5 Trouble Relay 12 NAC 10 11 TB4 F R R F F R R F F R R F F R R F 1 3 2 Input 1 EOL 10K 1 2W 5 6...

Page 27: ...sor M500CH Note Wiring shown must be in conduit and within 3 feet 6 7 8 9 2 1 3 Input 1 5 4 Input 2 12 Trouble Relay NAC 10 11 M P 4 3 2 1 M P 4 3 2 1 S I G S I G 401313 401314 401315 MODULE EOL 24K 1...

Page 28: ...tions including daisy chaining 4 1 Notification Appliance Power Applications Figure 4 1 Input 1 activates All Four Outputs and Input 2 not used Figure 4 2 Input 1 activates All Four Outputs and Input...

Page 29: ...Input 1 activates Outputs 1 2 3 and Input 2 activates Output 4 Figure 4 4 Input 1 activates Outputs 1 2 and Input 2 activates Outputs 3 4 120 VAC Input 1 Unit Fire Alarm Control Input 2 120 VAC Input...

Page 30: ...put 1 activates Outputs 1 2 3 4 as Class A and Input 2 used to silence Sync Horns Figure 4 7 Input 1 activates Output 1 2 as Class A and Input 2 activates Output 3 4 as Class A 120 VAC Input 1 Unit Fi...

Page 31: ...es required between units Fire Alarm Control Unit 120 VAC 2 1 3 Input 1 O u t p u t O u t p u t O u t p u t O u t p u t NAC Input 1 120 VAC 3 1 2 O u t p u t O u t p u t O u t p u t O u t p u t 120 VA...

Page 32: ...Figure 4 9 or Figure 4 10 must be used when synchronization of Sync Strobes Horns is required between NACs of different 15073s O u t p u t O u t p u t O u t p u t O u t p u t NAC 1 Non Silencable Fire...

Page 33: ...d when synchronization of Sync Strobes Horns is required between NACs of different 15073s O u t p u t O u t p u t O u t p u t O u t p u t NAC1 Non Silencable Fire Alarm Control Unit Input 1 120 VAC 1...

Page 34: ...tuations wire a normally closed relay contact from the fire alarm control unit in series with the auxiliary power to the door holders The circuit shown in Figure 4 11 will provide up to 3 amps of door...

Page 35: ...15073 OWNER S MANUAL 447179 Issue 1 Rev A 28 This page is intentionally blank firealarmresources com...

Page 36: ...tputs to wire as Style Z Class A and Style Y Class B Auxiliary power output operation on AC power fault Which outputs to operate as steady outputs or ANSI temporal Refer to Figure 2 2 for the location...

Page 37: ...controls output 4 Class B Switch 1 ON Switch 2 ON Switch 3 OFF Input 1 controls outputs 1 and 2 Class B Input 2 controls outputs 3 and 4 Class B Switch 1 OFF Switch 2 OFF Switch 3 ON Input 1 controls...

Page 38: ...when powering up If you change this switch you must push switch SW2 momentarily to reset the unit to recognize the new switch setting Switch 4 OFF Auxiliary Power Output always on Switch 4 ON Auxilia...

Page 39: ...Output Relationship Switch 5 OFF Switch 6 OFF Slave Operation Input 1 s outputs will follow the input pattern steady in coded march time temporal or Sync Switch 5 ON Switch 6 OFF Master Temporal Opera...

Page 40: ...4 OFF without removing power Remember to turn the switch ON when testing is complete Switch 9 OFF Switch 10 OFF AC power fault reporting will not be delayed Switch 9 ON Switch 10 OFF AC power fault r...

Page 41: ...n J5 must be set the same 1 Class B 2 3 Class A J5 NAC 1 2 Configuration J4 must be set the same 1 Class B 2 3 Class A J7 NAC 3 4 Configuration J8 must be set the same 1 Class B 2 3 Class A J8 NAC 3 4...

Page 42: ...Wire Selection Guide Each Notification Appliance Circuit must not have a voltage drop greater than 1 5V The following chart is based on the following premises The entire load is at the end of the wire...

Page 43: ...Hour 0 240 AH 15 Hour 0 600 AH 24 Hour 0 960 AH A H for Standby A x ____ Hours Total Alarm Current from above 5 Minutes of Alarm Operation per NFPA 72 Standard AH for Alarm A x 0 0833 Hours A H for S...

Page 44: ...Sync Strobe Light 20 31VDC 0 088A 2701 T 2 Sync Strobe Light 20 31VDC 0 154A 2701 Y 2 Sync Strobe Light 20 31VDC 0 170A 2701 Z 2 Sync Strobe Light 20 31VDC 0 249A 2705 E WP Strobe Light 20 31VDC 0 059...

Page 45: ...A 4 5383 Electronic Signal 8T 12 32VDC 0 020 0 050A 4 5384 Electronic Signal 8T 12 32VDC 0 020 0 050A 4 5385 Electronic Signal 8T 12 32VDC 0 020 0 050A 4 5405 Sync Control Unit 20 31VDC 020A 5406 Sync...

Page 46: ...orn w Sync Strobe 21 30VDC 0 065A 20 31VDC 0 154A 6258 Y 2 Horn w Sync Strobe 21 30VDC 0 065A 20 31VDC 0 170A 6258 Z 2 Horn w Sync Strobe 21 30VDC 0 065A 20 31VDC 0 249A 6300 Mini Horn 20 31VDC 0 025A...

Page 47: ...Sync Strobe Light UL1971 60 75cd Cat No xxxx K Strobe Light UL1971 75cd Cat No xxxx Y Sync Strobe Light UL1971 75cd Cat No xxxx L Strobe Light UL1971 110cd Cat No xxxx Z Sync Strobe Light UL1971 110c...

Page 48: ...day LLC R711 1 711 1 Remote Relay Unit Air Products Controls R712 1 MR 101 C Remote Relay Unit R712 2 MR 201 C Remote Relay Unit R712 4 MR 104 C Remote Relay Unit R712 8 MR 204 C Remote Relay Unit 927...

Page 49: ...45681 227 0 086m 100mA Must use EOL Relay 9222 w 9266 55000 380 w 45681 227 0 205m 100mA Must use EOL Relay System Sensor 9337 1112 24 0 050mA 25mA Must use EOL Relay 9338 2112 24 0 050mA 25mA Must us...

Page 50: ...lows DESIGNATION MARKING COLOR DESCRIPTION DS1 OUTPUT1 Yellow NAC 1 trouble LED DS2 OUTPUT2 Yellow NAC 2 trouble LED DS3 OUTPUT3 Yellow NAC 3 trouble LED DS4 OUTPUT4 Yellow NAC 4 trouble LED DS5 AUX P...

Page 51: ...han 21 4VDC No battery input power Shorted battery input Open polyswitch F2 or F3 Disconnect battery and reconnect to reset Note The battery input is checked about once a minute for troubles and resto...

Page 52: ...cted Labeled Equipment or materials to which have been attached a label symbol or other identifying mark of an organization acceptable to the authority having jurisdiction and concerned with product e...

Page 53: ...Faraday LLC 805 South Maumee Street Tecumseh Michigan 49286 Phone 517 423 2111 Fax 517 423 2320 Copyright 2000 Faraday LLC All Rights Reserved P N 315 099082FA 2 firealarmresources com...

Reviews: