15073 OWNER’S MANUAL
447179 Issue 1 Rev. A
33
5.1.4
Setting the AC Power Fault Reporting Delay
Normal selection for reporting loss of AC is 6 hours.
The OFF position is for test purposes only and the normal position for switch 9 is ON. For testing the Low
AC reporting, you can temporarily turn switch 4 OFF without removing power.
Remember to turn the switch ON when testing is complete.
Switch 9 OFF & Switch 10 OFF:
AC power fault reporting will not be delayed.
Switch 9 ON & Switch 10 OFF:
AC power fault reporting will be delayed 6 hours.
Switch 9 OFF & Switch 10 ON:
AC power fault reporting will be delayed 15 hours.
Switch 9 ON & Switch 10 ON:
AC power fault reporting will be delayed 24 hours.
Figure 5-5. Setting DIP Switch 9 and 10
10
9
8
7
6
6
7
8
9
10
ON
OFF
6
7
8
9
10
6
7
8
9
10