Note on Pipe Length
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal
efficiency is tested on units with a pipe length of 5 meters.
A minimum pipe run of 3 metres is required to minimise vibration & excessive noise.
Connection Instructions – Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra
care to cut and flare them properly. This will
ensure efficient operation and minimize the
need for future maintenance.
1. Measure the distance between the indoor
and outdoor units.
Refer to the table below for specifications on the maximum length and drop height of piping.
When connecting refrigerant piping,
do not
let substances or gases other than the specified
refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity,
and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and
injury.
2.
Using a pipe cutter, cut the pipe a little longer
than the measured distance.
3.
Make sure that the pipe is cut at a perfect 90°
angle.
Oblique Rough Warped
90°
DO NOT DEFORM PIPE
WHILE CUTTING
Be extra careful not to damage, dent, or
deform the pipe while cutting. This will
drastically reduce the heating efficiency
of the unit.
Refrigerant Piping Connection
Refrigerant
Piping
Connection
Pipes requirements (R32 refrigerant)
Model
Pipes
FW12-2250
FW12-3000
FW12-4500
FW12-6000
1/4"
Liquid
Gas
3/8"
1/4"
3/8"
1/4"
1/2"
3/8"
5/8"
Max. Length
(m)
25
25
30
50
Drop Height
(m)
10
10
20
25
Refrigerant
preload (m)
5
5
5
5
Additional
refrigerant (g/m)
12
12
12
24
92
Summary of Contents for FW12 Series
Page 44: ...Control remoto Informaci n Previa a su Utilizaci n 44...
Page 48: ...Control remoto 48...
Page 49: ...Control remoto 49...
Page 50: ...Control remoto 50...
Page 52: ...Control remoto 52...
Page 53: ...Control remoto Funci n Silence 53...
Page 288: ...C ROSSELL 430 432 08025 BARCELONA ESPA A SPAIN SAT 34 93 652 53 57 34 93 446 27 80...