4

O P E R A T I O N

S i c u r g a s

IMPULSE RELAY, WITH CURRENT ACTIVATION, 

TO CONTROL A NORMALLY OPENED VALVE WITH  

MANUAL RESET (SWITCH IN UP POSITION)

The connection will ensure the interruption of the 

gas inflow in case of gas concentration threshold 

exceeding.

Sicurgas is provided with a TEST/SILENCING key, that allows to check the installation or to inhibit the 

alarm. This key is activated through a cord for P11 methane gas (installed about 30 cm from the ceiling) or 

through a button located on the body of P12 LPG (installed about 30cm from the floor).

To test the installation press the TEST/SILENCING key for 10 sec. In this way will be activated a control 

procedure of about  30 sec., during which will be checked installation components.

Alarm inhibition is used instead to avoid an involuntary intervention of the detector, in fact Sicurgas  sensor, 

as all available on the market sensors, while being very selective can also participate for other substances, 

for example: alcohol vapors, wine etc.

For example, during the use of wine while preparing food is possible, that the detector will enter in alarm 

situation. To avoid this inconvenience press the TEST/SILENCING key for approx. 3 sec.

After having pressed the silencing key, for 10 minutes we will have a non-alarm situation: the buzzer 

does not emits acoustic signaling, the relay returns in non-alarm position and the red and green led,  are 

flashing alternately to indicate the silence period; acting again on the switch during 10 minutes of the 

USING MORE SICURGAS UNITS TO CONTROL 

SEVERAL ROOMS WITH ONE GAS VALVE

Example of connection for several Sicurgas 

detectors with stable relay that controls the same 

normally closed valve NC and an external alarm. 

The contacts must be connected in series.

Example of connection for several Sicurgas 

detectors with impulse relay which controls the 

same normally opened valve NA. The contacts 

must be connected in parallel.

5

6

PLUG IN THE POWER SUPPLY  (230Vc.a. 50Hz).

DEVICE CONTROL AND SILENCING ALARM

OPERATION

At the first detector switch-on and after any power 

supply failure, Sicurgas enters into pre-heating 

and a sensor stabilization phase that continues 

maximum 3 minutes. During this period will flash 

alternately the red and green led indicating that the 

device is not ready yet for gas detection. After this 

period just the green led will remain switched on.

test/ 

silencing key (cord for P11)

L
N

L

N

L

N

230Vc.a. - 50Hz

230Vc.a. - 50Hz

230Vc.a. - 50Hz

NA

NC

NA

Summary of Contents for P11

Page 1: ...AS LEAK DETECTORS FOR METHANE AND LPG INSTRUCTIONS FOR USE FANTINI COSMI S p A Via dell Osio 6 20090 Caleppio di Settala Milano ITALY Tel 39 02 956821 Fax 39 02 95307006 info fantinicosmi it www fanti...

Page 2: ...3 modules or in round boxes Remove the base cover retaining screw and ease off the cover Fix the base on the wall see paragraph 3 or in a built in box using rear entry for the entries of the connecti...

Page 3: ...guarantees maximum safety the gas inflow will be stopped in case of gas concentration threshold exceeding power supply lack of the valve only or of the detector connection breakdown between the detec...

Page 4: ...s inconvenience press the TEST SILENCING key for approx 3 sec After having pressed the silencing key for 10 minutes we will have a non alarm situation the buzzer does not emits acoustic signaling the...

Page 5: ...not switch on or off lights do not operate electrical equipments or other electrically operated devices 4 open the windows and the doors to raise the ventilation inside the room 5 do not use telephon...

Page 6: ...6 N O T E S S i c u r g a s...

Page 7: ...facilities A black bar indicates that the product was placed on the market after 13 August 2005 Participating in the separate collection of products and batteries contributes to the correct disposal...

Page 8: ...ment date sensor replacement date is indicated on the front cover label N B THE DETECTOR HAS TO BE REPLACED AFTER A PERIOD OF FIVE YEARS FROM THE INSTALLATION DATE STAMP AND SIGNATURE OF THE INSTALLER...

Reviews: