READ THESE INSTRUCTIONS COMPLETELY BEFORE INSTALLING THE FAN AND SAVE THE INSTRUCTIONS FOR FUTURE REFERENCE.  
IT IS RECOMMENDED THAT THESE FANS BE INSTALLED BY LICENSED PROFESSIONAL TRADESPERSONS.

Upon receiving the unit, check for any damage and report it immediately to the shipper. Also insure all accessory items are accounted for.

Move fan to desired location and determine the method by which the fan is to be mounted as shown in the illustrations below.  Optional Wall Housings
and Wall Mounting Collars provide a convenient means of mounting sidewall fans while maintaining the proper distance between the propeller and
damper.

Attach the fan by inserting a suitable fastener through each of the pre-punched mounting holes in the fan panel.  Care should be taken not to bend or
distort the fan panel or damage drive components during installation.  belt-drive fans mounted direct to walls will require suitable attachment holes
drilled around the perimeter of the fan panel.

The motor voltage and amperage must be checked for compatibility with the electrical supply.  
Supply wiring to the unit must be properly fused and conform to local and national electrical codes.

TYPICAL INSTALLATIONS

Wall opening size and propeller-to-damper distance are two important dimensions for fan installation.  Fans mounted to the wall require a different
opening (W.O.) than those mounted in wall housings or wall collars.  Propeller-to-damper distance is important to reduce turbulence and damper flutter
which may lead to premature damper failure.  

Illustrations #1 and #2 show the wall opening (W.O.1) required for installations with either wall housing or a wall collar.  Illustration #3 shows the rec-
ommended wall opening (W.O.2) and the minimum (M) distance suggested between the fan and damper for direct to wall installations.

Additional

support or bracing (by others) may be required to support mounted fans.

WALL OPENING REQUIREMENTS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL
FOR FADE, TABE & THDAB

#1 

Wall Housing Installation

#2 

Wall Collar Installation

#3 

Direct to Wall Installation

W.O.1

W.O.1

W.O.2

READ & SAVE THESE INSTRUCTIONS!

Fan Model

W.O.1

Damper

W.O.2

Damper

M i n i m u m

FADE

TABE

THDAB

Sq

Sq

Sq

Sq

Distance

8

N/A

N/A

9 1/2

9

6

10

N/A

N/A

11

10

7

12

21 1/2

18

13 1/2

12

7

14

21 1/2

18

16 1/2

16

8

16

24 1/2

21

18 1/2

18

9

18

24 1/2

21

21 1/2

21

9

20

26 1/2

21

21 1/2

21

10

22

32 1/2

26

26 1/2

26

11

25

32 1/2

26

26 1/2

26

12

20

25 1/2

20

22

20

10

24

24

31 1/2

26

28

26

11

30

30

37 1/2

32

34

32

14

36

36

43 1/2

38

40

38

14

42

42

49 1/2

44

46

44

15

48

48

55 1/2

50

52

50

16

54

54

61 1/2

56

58

56

19

60

60

67 1/2

62

64

62

20

72

81 1/2

76

78

76

26

M

Summary of Contents for FADE Series

Page 1: ......

Page 2: ...DE 18 FADE 20 6 FADE 20 4 109290 FADE 22 FADE 25 109292 109286 109293 109287 109294 109288 109295 109289 109297 109291 109285 109300 FarmTek Stock Numbers Copyright 2009 FarmTek 1440 Field of Dreams Way Dyersville IA 52040 http www farmtek com ...

Page 3: ...ovide for vibration free performance Performance Fan performance shall be based on tests conducted in accordance with AMCA Standards 210 300 and 301 and shall be licensed to bear the AMCA Certified Ratings label for both sound and air Code Approval Fan shall be tested and approved by UL or equal for safety FADE Series shall be manufactured under the authority of Fantech Inc Sarasota FL Features 100...

Page 4: ...hown are for inlet Lwi and inlet LwiA sound power levels for installation type A Free inlet Free outlet Ratings include the effects of duct end correction for inlet duct Speed RPM shown is nominal Performance ratings include the effect of inlet guard Performance certified is for installation type A free inlet free outlet Dimensions in inches Fantech Inc certifies that the FADE Series shown herein is...

Page 5: ...e in inches W G The sound power level ratings shown are in decibels referred to 10 12 watts calculated per AMCA Standard 301 Values shown are for inlet Lwi and inlet LwiA sound power levels for installation type A Free inlet Free outlet Ratings include the effects of duct end correction for inlet duct Sound Power re 10 12 Watts Model Nom SP Octave Bands Hz Lwi Sones RPM 63 125 250 500 1000 2000 40...

Page 6: ...nch thick aluminum HD 28 gauge galvanized steel Seals Extruded vinyl mechanically locked into blades Axles Stainless steel Linkage Stainless steel pins galvanized steel tie bar Finish Mill ACCESSORIES Dimensions Fan Louvered Dampers Actuator Loose Damper Model Loose w Collar 120V A B C 8 GDV 9 9 11 3 10 GDV 10 10 12 3 12 GDV 12 GDV 18 MP2781A 12 14 3 14 GDV 16 GDV 18 MP2781A 16 18 3 16 GDV 18 GDV ...

Page 7: ...cific legal rights and are subject to an applicable consumer protection legislation You may have additional rights which vary from state to state Limitation of Warranty and Liability This warranty does not apply to any FANTECH INC product or part which has failed as a result of faulty installation or abuse incorrect electrical con nections or alterations made by others or use under abnormal operati...

Page 8: ... Ordering Now Fantech offers two ways to order the FADE Series Use the Fan Only model numbers to order fan alone or use the new Fully Assembled model numbers and you ll receive the Fan fully assembled with wall collar and backdraft damper Easy Set Up In most installations no extras are required Note Assembled units will require bracing by others if installed in a metal building External Rotor Moto...

Page 9: ...he NB E4S 3M5 1 800 565 3548 www fantech ca Fantech reserves the right to modify at any time and without notice any or all of its products features designs components and specifications to maintain their technological leadership position Item 450527 Rev Date 011008 AIR PERFORMANCE GRAPHS 0 0 00 0 10 0 20 0 30 0 40 0 50 0 60 0 70 0 0 00 0 20 0 40 0 60 0 80 1 00 1 20 3500 3000 2500 2000 1500 1000 50...

Page 10: ...eller to damper distance are two important dimensions for fan installation Fans mounted to the wall require a different opening W O than those mounted in wall housings or wall collars Propeller to damper distance is important to reduce turbulence and damper flutter which may lead to premature damper failure Illustrations 1 and 2 show the wall opening W O 1 required for installations with either wa...

Page 11: ...INGS BELT DRIVE FANS ONLY All Fantech belt drive fans have self aligning cast iron pillow block type bearings with re lube fittings of the air handler type L50 200 000 hour average life Bearings should be inspected at periodic intervals Locking collars and set screws in addition to fasteners attaching the bearings to the bearing plate or mounting frame must be checked for tightness Selection of th...

Page 12: ...ntrary is expressly set forth herein It is understood that such statements were not intended to and did not form a part of the agreement they were merely made in the course of negotiations of the parties THIS WARRANTY IS IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTIES INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE OUR SOLE AND EXCLUSIVE OBLIGATION UNDER ...

Page 13: ...e wire according to the code on the band 2 Color of capacitor leads may be reversed Fan operation will not be affected 230 Volt Three Phase Fans Notes 1 Contactor should be used Control coil should be wired in series with motor ther mal contacts TK leads as shown in diagram to provide thermal motor protection 2 All leads are color coded as well as identified with a band con taining an Alpha Alpha ...