Installation on Metal Deck: 

 

1.

 

Installation of this product should be carried out by appropriately qualified persons. 

2.

 

 Cut a hole in the roof 200mm minimum (with regard to roof pitch angle) diameter.  The hole should be 

positioned adjacent to a rafter or other member to facilitate the use of the mounting brackets supplied.  

Ensure a clean edge. 

3.

 

Cut the rubber roof flashing supplied for 190mm diameter through roof duct. 

4.

 

Slide the flashing over the through roof duct to the required position. 

5.

 

Check the fit of the duct in the cut hole.  The duct must be positioned vertically. 

6.

 

If satisfactory fasten the duct to the rafter or other member using the mounting brackets provided. 

7.

 

Fit the flashing to the metal deck using the mounting screws provided.  Seal duct seam with sealant. 

8.

 

 The vent through roof duct is designed for connection to 200mm duct using duct tape or clamps.  

 

Installation on 

Tiles

 

 

 
Installation on Tiles: 

 

1.

 

 Installation of this product should be carried out by appropriately qualified persons. 

2.

 

 Prepare an opening in the tiled roof 220mm minimum (with regard to roof pitch angle) diameter.  The 

hole should be positioned adjacent to a rafter or other member to facilitate the use of the mounting 

brackets supplied. 

3.

 

Cut the rubber roof flashing supplied for 190mm diameter through roof duct. 

4.

 

Slide the flashing over the through roof duct to the required position. 

5.

 

Check the fit of the duct in the opening.  The duct must be positioned vertically. 

6.

 

If satisfactory fasten the duct to the rafter or other member using the mounting brackets provided. 

7.

 

Fit the upper edge of the flashing underneath the tile, bending over top edge to form an anti-capillary 

barrier. 

8.

 

Cut two tabs in the corners of the lower section and turn under tile (refer detail).  Lay the lower section 

of the flashing over tiles and form a run off tray.  Form to tiles.  Seal duct seam with sealant. 

9.

 

 The vent through roof duct is designed for connection to 200mm duct using duct tape or clamps.  

 