On standby. The recloser can leave this mode via three conditions:
•
Recloser lock, via a command.
•
Manual or remote control opening of the circuit breaker. In this situation it shall await the final
opening of the same, and then it shall switch to lock mode.
•
Circuit breaker trip. This shall start the reclosing cycles. This start may arise either from the
trip itself, or from an external input if external protection is fitted.
When locked. The recloser shall switch from this condition as a result of two different conditions:
•
Manual or remote control closing of the circuit breaker. In this case it shall switch to safety
time. If, during this time, there is a trip, it shall revert to Lockout.
•
Unlocking of the recloser. Via a command.
Of all the remaining conditions, it is interesting to know that the recloser sends a closure
command whilst it is in the Close Time condition, and for this reason if you wish to programme
an output on said command, the output must be set to the 79 closing time bit.
The “79 init” status is an adjustable logical signal.
4.10.1. Counter to record the number of reclosings
The SIL-D equipment is fitted with a counter that records the number of reclosings.
Summary of Contents for SIL-D00
Page 8: ...www fanox com Rev 06 8 226 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 06 9 226 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 06 10 226 2 3 Cut out pattern...
Page 12: ...www fanox com Rev 06 12 226 Digital connections Only as an example...
Page 13: ...www fanox com Rev 06 13 226 2 5 Terminals...
Page 49: ...www fanox com Rev 06 49 226...
Page 50: ...www fanox com Rev 06 50 226...
Page 51: ...www fanox com Rev 06 51 226...
Page 52: ...www fanox com Rev 06 52 226...
Page 200: ...www fanox com Rev 06 200 226...
Page 225: ...www fanox com Rev 06 225 226 NOTES...
Page 226: ...www fanox com Rev 06 226 226...