5.5.
Self-diagnosis
Diagnostic algorithms are run while the equipment is being started up and continuously when
the relay is operating. This diagnostic is a preventative process to guarantee that the equipment
is in good operational condition.
As general considerations we can establish:
Communications among the different processors are confirmed by corresponding
integrity checks. In case of having continued anomalies, the equipment would reset.
Information data which is considered
“setting parameters” is confirmed by the
corresponding checks. In this way, all the setting tables are doubled and the relay is
able to work with one broken table but not two.
There is a mechanism of WatchDog,
among the different main CPU’s. The loss of
activity for any of them would mean the equipment reset, remaining as an event in the
memory.
The following status bits are associated with this process:
Trip power error
Problem in the voltage of trip circuit
Measurement error
Problem in the measurement block
Protection error
Problem in the protection block
Eeprom error
Problem in the eeprom memory, default settings
On the other
hand, “Settings by default” indicates that the relay is working with the settings
programmed in factory, being all the protection functions disabled.
5.6.
Date-time synchronisation
All models of relay SIA-C are provided with a real time clock (RTC), which can be synchronized
by HMI or by communications. RTC keeps the data updated during at least 72 hours without
power supply. Charge time for the capacitor is 10 minutes.
This clock can be synchronized by two ways:
By HMI: in this case, it is allowed to register the date and the time by using the keys on the
front panel. The relay will save a new event indicating the synchronization.
Protocol. The behaviour is similar to HMI, the relay synchronizes date and time and saves a
new synchronization event.
Summary of Contents for SIA-C
Page 1: ...Sia_Manu_Siac_Ing_R026 USER S MANUAL SIA C Dual Self powered overcurrent earth fault relay...
Page 9: ...www fanox com Rev 26 9 188 Cut out pattern...
Page 10: ...www fanox com Rev 26 10 188 2 2 Case Dimensions mm of SIA C with mechanics type B and C...
Page 11: ...www fanox com Rev 26 11 188 Cut out pattern...
Page 15: ...www fanox com Rev 26 15 188 2 6 KITCOM Dimensions...
Page 16: ...www fanox com Rev 26 16 188 2 7 Striker Dimensions in mm A 44 5 B 49 5 C 56 5 D 64 5 E 42 5...
Page 17: ...www fanox com Rev 26 17 188 2 8 TCM Dimensions...
Page 29: ...www fanox com Rev 26 29 188 3 phase transformers Power supply and measurement solid neutral...
Page 42: ...www fanox com Rev 26 42 188 2 10 2 Physical layout of SIA C types B and C terminals...
Page 46: ...www fanox com Rev 26 46 188 2 10 3 Physical layout of SIA C type E terminals...
Page 74: ...www fanox com Rev 26 74 188...
Page 75: ...www fanox com Rev 26 75 188...
Page 76: ...www fanox com Rev 26 76 188...
Page 77: ...www fanox com Rev 26 77 188...
Page 79: ...www fanox com Rev 26 79 188...
Page 80: ...www fanox com Rev 26 80 188...
Page 81: ...www fanox com Rev 26 81 188...
Page 126: ...www fanox com Rev 26 126 188 Connection diagram for a RS485 bus...
Page 187: ...www fanox com Rev 26 187 188 NOTES...
Page 188: ...www fanox com Rev 26 188 188...