4.13. Application examples
It is important to know that if both overcurrent protection functions (50 and 50/51), phase or neutral,
are enable, definite time function (function 50) must be more restrictive. So, if overcurrent fault
values are low, inverse time overcurrent function (function 50/51) must work, and if overcurrent fault
reaches a certain value, definite time overcurrent function will always work. This is because, when
overcurrent fault reach high values (I>>), it is necessary to be sure that trip is going to be
instantaneous to get that the element we are protecting, does not be damaged.
It is shown somo examples below:
APPLICATION EXAMPLE 1
Starting from the following information:
Line details:
Transformation ratio of CT =100/1
Primary current: I
p
=100 A
50/51 function settings
Curve type: IEC Inverse
Dial: 0.05
Tap: 1xI
n
50 function settings
Tap: 11xI
n
Operating time: 0.05 s
Figure 1. 50 and 50/51 IEC Inverse
If overcurrent fault is 11xI
n
=1100 Ap, IEC inverse curve defines a tripping value of 0.1425s (Figure1)
for 50/51 function. It is considered that this time is too high, so when current fault reaches 11xI
n
,
definite time overcurrent function will be work.
Summary of Contents for SIA-C
Page 1: ...Sia_Manu_Siac_Ing_R026 USER S MANUAL SIA C Dual Self powered overcurrent earth fault relay...
Page 9: ...www fanox com Rev 26 9 188 Cut out pattern...
Page 10: ...www fanox com Rev 26 10 188 2 2 Case Dimensions mm of SIA C with mechanics type B and C...
Page 11: ...www fanox com Rev 26 11 188 Cut out pattern...
Page 15: ...www fanox com Rev 26 15 188 2 6 KITCOM Dimensions...
Page 16: ...www fanox com Rev 26 16 188 2 7 Striker Dimensions in mm A 44 5 B 49 5 C 56 5 D 64 5 E 42 5...
Page 17: ...www fanox com Rev 26 17 188 2 8 TCM Dimensions...
Page 29: ...www fanox com Rev 26 29 188 3 phase transformers Power supply and measurement solid neutral...
Page 42: ...www fanox com Rev 26 42 188 2 10 2 Physical layout of SIA C types B and C terminals...
Page 46: ...www fanox com Rev 26 46 188 2 10 3 Physical layout of SIA C type E terminals...
Page 74: ...www fanox com Rev 26 74 188...
Page 75: ...www fanox com Rev 26 75 188...
Page 76: ...www fanox com Rev 26 76 188...
Page 77: ...www fanox com Rev 26 77 188...
Page 79: ...www fanox com Rev 26 79 188...
Page 80: ...www fanox com Rev 26 80 188...
Page 81: ...www fanox com Rev 26 81 188...
Page 126: ...www fanox com Rev 26 126 188 Connection diagram for a RS485 bus...
Page 187: ...www fanox com Rev 26 187 188 NOTES...
Page 188: ...www fanox com Rev 26 188 188...