Chapter 8 Diagnosis Function
67
Move the cursor to the corresponding date, time or week, press
【↑】
or
【↓】
to
adjust the time.
8.7 System Definition
In the system diagnosis interface, press F8 to enter the system custom definition
interface, in the interface, you could set the input IO, output IO or system coordinate, also
reset or backup the parameters and one key switch between English or Chinese.
8.7.1 Parameter Backup and Restore
Parameter Backup: The process of parameter backup is, in the main interface press
【
F5
】
(System Diagnosis),
【
F8
】
( System Definition),
【
F2
】
(Parameter Backup). The
system will need code, after inputting the code “1396”, press
【
Enter
】
, the system will
import the default parameters. In the following process, if the parameters are modified or
some of them is broken, reset the parameters.
Warning: after installing and debugging the complete equipment, equipment
manufacturer please backup the parameters.
Parameter Reset: The process of reset the parameters is, press
【
F5
】
(System
Diagnosis) in the main interface,
【
F8
】
(System Definition),
【
F1
】
(Parameter Reset).
Warning: After resetting successfully, please restart the system.
8.7.2 Input Definition
The controller could change the IO definition, including changing the order of IO
number, the type of IO( normally open or closed) according to the user’s need. In the
system custom definition interface, press
【
F3
】
to enter the definition interface, press
【
F1
】
to enter the input definition interface. As shown in fig 8.8.