F&U PAH-1218 Instruction Manual Download Page 15

                                                                                                                                                                                                                                               
 

Page:15/20                                                                                                                                               

 

15 

for    use    with    most    refrigerants    but    the    use    of    detergents containing chlorine shall be avoided 
as the chlorine may react with the   
refrigerant and corrode the copper pipe-work.     
If a leak is suspected, all naked flames shall be removed / extinguished.     
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the 
system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free 
nitrogen (OFN) shall then be purged through the system both before and during the brazing process. 
 
7. 

Removal and evacuation

 

When  breaking  into  the  refrigerant  circuit  to  make  repairs  –  or  for  any  other  purpose  –  conventional 
procedures  shall be used. However, it is important that best practice is followed since flammability is a 
consideration. The following procedure shall be adhered to:   
• Remove refrigerant;     
• Purge the circuit with inert gas;       
• Evacuate;     
• Purge again with inert gas;     
• Open the circuit by cutting or brazing.     
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed” 
with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or 
oxygen shall not be used for this task.      Flushing shall be achieved by breaking the vacuum in the system 
with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and 
finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. 
When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable 
work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take 
place.     
Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation 
available. 
 

8. Charging procedures 

In addition to conventional charging procedures, the following requirements shall be followed.     
–  Ensure  that  contamination  of  different  refrigerants  does  not  occur  when  using  charging  equipment. 
Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them.     
– Cylinders shall be kept upright.       
– Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.     
– Label the system when charging is complete (if not already).       
– Extreme care shall be taken not to overfill the refrigeration system.     
Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on 
completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving 
the site. 

 

9. Decommissioning 

Before  carrying  out  this  procedure,  it  is  essential  that  the  technician  is  completely  familiar  with  the 
equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. 
Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required 
prior to re-use of reclaimed refrigerant. It is   
essential that electrical power is available before the task is commenced.     
a) Become familiar with the equipment and its operation.       

Summary of Contents for PAH-1218

Page 1: ...LOCAL AIR CONDITIONER PAH 1218 Instructions Manual Read and save these instructions ...

Page 2: ...n 6 V Installation and adjustment 7 VI Drainage Instructions 9 VII Maintenance 10 VIII Out of season save 10 IX Troubleshooting 11 X Addendum 11 Please read these instructions before use and repair The drawings provided in this manual may not be the same as the physical objects Please refer to the physical objects ...

Page 3: ...ce and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants 12 All working procedure that affects safety means shall only be carried by competent persons Notes The air conditioning is only suitable for indoor use and is not suitable for other applications Follow local grid interconnection ...

Page 4: ...eaning and maintenance shall not be made by children without supervision If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The appliance shall be installed in accordance with national wiring regulations Do not operate your air conditioner in a wet room such as a bathroom or laundry room Transportation m...

Page 5: ...unction Protection function of automatically restarting the compressor after three minutes a variety of other protection functions Max operation temperature for the air conditioner Cooling 35 24 heating 20 12 Temperature operation range 7 35 2 Components ...

Page 6: ...case of power on press the key to turn off the machine in the case of power off press the key to turn on the machine 3 Mode Selection Key In the case of power on press the key to switch between cooling dehumidification fan heating single cold with no such function cooling mode 4 Up Key and Down Key press the two keys to change the set temperature or timer set value Exhaust Pipe Assembly Window Sea...

Page 7: ...d speed operation In dehumidification mode pressing the key is invalid and the fan will forcibly choose low wind speed operation 6 Timer Key In the case of power on press the key to set turn OFF timer in the case of power off press the key to set turn ON timer Press the key when the timer symbol flashes press up and down key to select the required timer value Timer values can be set within 1 24 ho...

Page 8: ...o normal operation 3 2 Overflow Protection Function When water in the water pan exceeds the warning level the machine will automatically sound an alarm and the FULL indicator light will flash At this point you need to move the drainage pipe connecting the machine or the water outlet to sewer or other drainage area to empty the water details see Drainage Instructions at the end of this chapter Afte...

Page 9: ...d in horizontal and vertical direction 2 Pull various components of the window sealing plate assembly open adjust their opening distance to bring both ends of the assembly into contact with the window frame and fix various components of the assembly 1 2 Install the window sealing plate assembly Notes 1 the flat end of the exhaust pipe joints must be snapped into place 2 The pipe cannot be distorte...

Page 10: ...ice The length of the exhaust hose shall be 280 1 500mm and this length is based on the specifications of the air conditioning Do not use extension tubes or replace it with other different hoses or this may cause a malfunction Exhaust host must be not blocked otherwise it may cause overheating VI Drainage Instructions This machine has two drainage methods manual drainage and continuous drainage 1 ...

Page 11: ...e water plug and tighten the drainage cover 2 Continuous drainage Optional only applicable to dehumidifying mode as shown in figure 1 Unscrew the drainage cover and unplug the water plug 2 Set the drainage pipe into the water outlet 3 Connect the drainage pipe to the bucket VII Maintenance Cleaning before cleaning and maintenance turn off the machine and unplug the plug 1 Clean the surface Clean w...

Page 12: ...ioning with a plastic bag Put the air conditioning in a dry place keep it out of the reach of children and take dust control measures vi Remove batteries of the remote control and keep them properly Note ensure that the body is placed in a dry place and keep all machine components properly 1 Information on servicing 1 Checks to the area Prior to beginning work on systems containing flammable refri...

Page 13: ...The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere 8 Checks to the refrigeration equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s tech...

Page 14: ...3 Repair to intrinsically safe components Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere The test apparatus shall be at the correct rati...

Page 15: ...l no refrigerant is within the system When the final OFN charge is used the system shall be vented down to atmospheric pressure to enable work to take place This operation is absolutely vital if brazing operations on the pipe work are to take place Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available 8 Charging procedures In addition to...

Page 16: ...rant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders for holding the total system charge is available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve a...

Page 17: ...e pipe becomes dry so as to keep the inside of the body in a dry state and prevent it from mildewing 3 Turn off the machine unplug the power plug and wrap the power cord around the wrapping post install the water plug and the drainage cover 4 Remove the exhaust pipe and keep it properly 5 Cover the air conditioning with a plastic bag Put the air conditioning in a dry place keep it out of the reach...

Page 18: ...re other sources of heat Close doors and windows and add new air conditioning The filter screen is dirty Clean or replace the filter screen The air inlet or outlet is blocked Clear obstructions Big Noise The air conditioning is not placed on a flat surface Put the air conditioning on a flat and hard place to reduce noise compressor does not work Overheat protection starts Wait for 3 minutes until ...

Page 19: ...age 19 20 19 X Addendum Schematic diagram for air conditioning The specific technical parameters of the machine shall be subject to the nameplate on the product Condenser Compressor Evaporator Capillary ...

Page 20: ... are separate collection systems for used electrical and electronic products Please help us to conserve the environment we live in DECLARATION OF CONFORMITY Herewith Amiridis Savvidis S A states that this product complies with the requirements of below directives EMC Directive 14 30 EU Low Voltage Directive 14 35 EU ErP Directive 09 125 EC CE Marking 93 68 EEC RoHS Directive 11 65 EU The detailed ...

Reviews: