Wykres pracy

Main line

230 V AC mains supply

Reserve line

line supplied from the generator

Uk

voltage  of  contacts  control  and  load  switching 
(terminal 6)

Tor

start-up delay after switching on the power supply 
or resetting the lock signal (1÷2 seconds)

Tow

delay in disconnecting the line after a power failure

Top

switching time of the devices

Torg

generator start-up delay time (15 seconds)

Tk

generator start-up time

Tcprzyw

time to qualify a line as good (10 seconds)

Tp

time of switching the power supply from reserve to 
main input (0.3 seconds)

Control panel

be opened and the generator will be disconnected.

Features

control of supply line parameters;

* protection of receivers against too high or too low voltage;
* control of the relay contacts and protection against short-circuit 

of the generator with the main line;

* generator start up control;
* emergency, external safety switch;
* backup power supply of the controller from the battery together 

with the battery charging system

T

k

(s)

5

60

1

20

T(s)

1

5

10

15

U

min 

(V)

150

210

180

PF-441

L

L`

START

AL

UK 

Main line

Reserve

line

Lock

3-9

 

11-12

2-7

 

T

or

T

or

T

org

T

k

T

k

T

c

przyw

T

p

3

T

k

3

T

k

T

ow

T

op

SINGLE-PHASE BACKUP 

SWITCHING CONTROLLER

SZR-277

- 1 -

- 2 -

- 3 -

- 4 -

Purpose

The SZR-277 single-phase controller of backup switching is used to 
control the voltage of the single-phase power supply network and 
to switch the receiving line to the power supply from the generator 
in case of incorrect parameters of the main power supply line.

Functioning

If  the  mains  voltage  is  within  the  specified  range,  the  contact 
between  terminals  2-7  is  closed  and  the  mains  power  is 
transferred  to  the  receiving  line.  If  the  permissible  voltage 
parameters  are  exceeded,  the  contact  2-7  is  opened  and  the 
supply line is disconnected from reception. When the main line is 
disconnected, the generator starts up and then, by closing the 3-9 
contact, the power supply from the generator is transferred to the 
receiving line.If the power supply on the main line is restored and is 
within  the  specified  range  for  10  seconds,

 

the  contact  3-9

  will

5

9 0 2 4 3 1

6 7 2 4 6 5

Keep the product in a warm room for at least 2 hours 
before  connecting  it  to  the  mains  power  supply  (for 
storage  or  transport  at  low  temperatures)  to  prevent 
damage caused by condensation.

input status
indicators

generator status 

indicator

error

indicator

start up time 

controller

switch-off delay 

at too low 

power supply 

voltage

minimum 
permissible 
supply voltage

F&F Filipowski sp. j.

Konstantynowska 79/81   95-200 Pabianice   

phone/fax: (+48 42) 215 23 83 / 227 09 71    POLAND

http://www.fif.com.pl   e-mail: [email protected]

WARRANTY.

  The  F&F  products  are 

covered by a warranty of the 24 months   
from the date of purchase.  Effective only 
with proof of purchase. 
Contact your dealer or directly with us. 
More  information  how  to  make  a  com-
pliant can be found on the website:
www.fif.com.pl/reklamacje

Do not dispose of this device in the trash along with other waste! 

According 

to the Law on Waste, electro coming from households free of charge and can 
give any amount to up to that end point of collection, as well as to store the 
occasion of the purchase of new equipment (in accordance with the principle 
of old-for-new, regardless of brand). Electro thrown in the trash or abandoned 
in nature, pose a threat to the environment and human health.

Reviews: