- 3 -
The accrued value of the counter is reset in case of permanent
operation of the limiter longer than 10 minutes.
CTO trigger counter
This function controls the number of consecutive actuations of
the limiter. When the preset counter value is reached, the limit-
er disconnects the power supply permanently (no automatic re-
turn). The system can be switched on again after a manual reset
of the lock. By default (parameter 0) the limiter has the lockout
function set to 10 minutes after 5 consecutive disconnections.
The accrued value of the counter is reset in case of permanent
operation of the limiter longer than 10 minutes.
Operating mode
In operating mode, the display shows the value of the power
consumed. Led R indicates contact status: off - contact open
(position 7-9); on- contact closed (position 8-9). After pressing
the
„+�
button, the display shows the current measured voltage
value. After pressing the
„–�
button, the display shows the cur-
rent measured value of the disconnection counter.
Indication of emergency states
-UH
exceeding the upper voltage threshold
-UL
exceeding the lower voltage threshold
-O-
permanent disconnection when the disconnection
counter is exceeded
-P-/0.15
exceeding the threshold of the power consumption
limit. The information about the tripping and the
re-start time is displayed alternately and cyclically.