- 2 -

»

Automatic lock of the system power supply for 10 minutes in 

the case in case the power was exceeded fivefold;

»

Automatic power-off when the power consumption is 8 times 

higher than the set threshold value;

»

Automatic power-off when  the power consumption is great-

er than 16 kW;

»

Adjustable tripping time (1 s÷3 min.);

»

Adjustable reconnection time (4 s÷6 min.);

»

LED display for indicating power consumption and device 

configuration,

Power P

The power limiter allows you to power the circuit when the total 

power of the receivers in the controlled circuit is lower than the 

one set on the limiter scale. Exceeding the set power consump-

tion threshold in a controlled circuit results in a disconnection of 

the power supply to this circuit after a user-set time. The power 

supply will be restored automatically after a preset time. If the 

power consumed is still greater than the set value, the circuit will 

be disconnected again.

Automatic disconnection will also occur if the power consump-

tion is 8 times higher than the set threshold and if the power 

consumption exceeds 16 kW. The limiter is locked for 30 seconds.

Voltage UL/UH

This function controls the number of consecutive actuations of 

the limiter. When the preset counter value is reached, the limit-

er disconnects the power supply permanently (no automatic re-

turn). The system can be switched on again after a manual reset 

of the lock. By default (parameter 0) the limiter has the lockout 

function set to 10 minutes after 5  consecutive disconnections.

Functioning

Summary of Contents for OM-633

Page 1: ...ainst the rise of UL power supply voltage 230 260 V Counter of relay actuations with automatic disconnection of system power supply after exceeding a set number of actuations Purpose Features F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48 42 227 09 71 www fif com pl e mail biuro fif com pl Do not dispose of this device in the trash along with other w...

Page 2: ...led circuit results in a disconnection of the power supply to this circuit after a user set time The power supply will be restored automatically after a preset time If the power consumed is still greater than the set value the circuit will be disconnected again Automatic disconnection will also occur if the power consump tion is 8 times higher than the set threshold and if the power consumption ex...

Page 3: ... of permanent operation of the limiter longer than 10 minutes Operating mode In operating mode the display shows the value of the power consumed Led R indicates contact status off contact open position 7 9 on contact closed position 8 9 After pressing the button the display shows the current measured voltage value After pressing the button the display shows the cur rent measured value of the disco...

Page 4: ...n with the previous settings Restart After the power supply is switched on the limiter starts working after 10 seconds The display shows the remaining time to start Setting parameters P disconnection power range 1 10 kW step of 0 1 kW UH upper threshold of disconnection voltage range 230 260 V step of 5 V UL lower threshold of disconnection voltage range 150 210 V step of 5 V Cto disconnection cou...

Page 5: ...mode 1 Turn off the power supply 2 Fix the limiter on a rail in the control box 3 Connect the power supply of the limiter to terminals 1 2 It is essential to connect L to terminal 2 and N to ter minal 1 4 Connect the power supply of the controlled circuit or contac tor coil in series via terminals 8 9 5 Lead the control circuit cable through the through channel points 6 Set the operating parameter...

Page 6: ... 6 Connection diagram ...

Page 7: ... lower tripping threshold UL 150 210 V upper tripping threshold UH 230 260 V lower tripping time UL 5 s upper tripping time UH 0 3 s diameter of a through hole 5 mm power consumption 2 5 W working temperature 25 50 C terminal 2 5 mm screw terminals cord 4 0 mm screw terminals wire tightening torque 0 5 Nm dimensions 3 modules 52 5 mm installation on TH 35 rail ingress protection IP20 Technical dat...

Page 8: ... that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE Declaration of Conformity along with the references to the standards in relation to which confor mity is declared can be found at www fif com pl on the product page www fif com pl from the product subpage Warranty CE dec...

Reviews: