domestic and industrial automation
LE-01MR v.2 – User manual v.1.0.0
12
•
after passing the PIN verification, the first of the available configuration parameters -
Id
address
of the meter in the RS-485 network - is displayed;
•
the transition between the parameters is made by short pressing the button, long pressing takes
you to the edition of the selected parameter;
•
the parameter is set by short presses of the button, a long press of the button confirms the new
value.
No. Configuration parameters
Value
1 Meter address in the RS-485 net-
work
1
(default) – 247
2 Baud rate
6 – 9600 bps
(default)
7 – 19200 bps
8 – 38400 bps
9 – 57600 bps
10 – 76800 bps
11 – 115200 bps
3 Parity
0 – None
(default)
1 – Odd
2 – Even
4 Number of stop bits
Stop 1 – 1
(default)
Stop 2 – 2
5 Resetting the auxiliary active en-
ergy meter
The display cyclically shows the
reset
text and the current
value of the auxiliary meter. Press and hold down the button
on the front of the meter to reset the indication.
6 Resetting the auxiliary reactive en-
ergy meter
The display cyclically shows the
reset
text and the current
value of the auxiliary meter. Press and hold down the button
on the front of the meter to reset the indication.
7 Resetting the maximum active
power demand indicator
The registered value of the maximum active power demand
appears on the display as
P
Press and hold down the button on the front of the meter to
reset the indication.