PROG 6
HEATING mode- two regulators.
Second regulator dependent from first regulator.
Regulator work witg two sensors C1 and C2, whiches have
definited temperature T1 and T2 , and hysteresis thresholds H1 i
PROG 7
Differential regulator
Regulator work with two sensors C1 and C2. Ordered parameter
is distinction of temperatures. If distinction beteween reprts from
the first and second sensors (C1 C2) cross ordered value then
will be closed joint P1. If distinction of temperatures will be
smaller than ordered value then joint P2 will be close.
P1
P2
T1
T1 - H1
C1
T1 + H1
T2
T2 - H2
C2
T2 + H2
The first thermostat, is connect with sensor C1, it close when
temeratute from relay and output fall under value (T1-H1) and
open it when cross value (T1+H1). Position of the second
thermostat, which is connect with sensor C2 and outpu P2,
depend from position of the first thermostat and temerature from
sensor C2. Joint P2 will be closed when temperature from
sensor C2 will be smaller than value (T2-H2) and joint P1 will be
closed. Condition for open joint P2 is crossing by sensor C2 value
(T2+H2) or open joint P1 .
Ordered value.
P1
P2
(C1 - C2)
PROG 8
Window mode (one sensor)
Regulator work with sesor which is connect to joint C1. If
temperature from sensor will be in range definited by values T1
and T2, then realys joints P1 and P2 will be closed.
PROG 9
Window mode (two sensors)
Regulator works with two sensors C1 and C2. If temperature from
two sensors will be in range, which is definited by values T1
iandT2, then relay joints P1 and P2 will be closed.
C1
P1
P2
T1
T2
ATTENTION:
When will set value T2 > T1 then regulator will be
work correct.
PROG 10
Window mode - two regulators
Device works as two independent thermostats, which works in
window mode. Sensor Czujnik C1 dependent from parameter s
T1 and T2 and steer output of relay P1. Sensor C2 dependent
from parameters T3 and T4 i, steer output of relay P2 .
C1
C2
P1
P2
T1
T2
ATTENTION:
When will be set value T2 > T1 then regulator will
be work correct.
P1
P2
C1
T1
T3
C2
T4
T2
If temperature from sensor C1 will be included in range between
values T1 and T2, then joint of realy P1 will be close.Similary if
temperature from sensor C2 will be included in range between
values T3 iandT4, then joint of relay P2 will be close.
ATTENTION: When temerature will T2>T1, or T4 >T3, tthen
regulator doesn’t work correct
Menu -> SETTINGS
This menu is use to configuration parameters of regulator in
automatic work.
If you need edit parameters follow with procedure:
1. By button Menu pass to main menu.
2. By buttons “UP” or “DOWN” select menu Menu -> Settings and
enter OK..
3. By buttons “UP” or “DOWN” select parameter to edition and
prees OK...
4. By buttons “UP” or “DOWN” set value of parameter and enter
by OK..
5. Entered of change is signalize by raport: Saved with value of
saving parameter.
6. Possible is out from edition mode to main menu without save all
changes by button return.