- 11 -
The changeover contact of the relay allows to connect
a visual or audible signalling system that informs abo-
ut the relay activation, which means switching off the
motor.
power supply
3×400 V+N
contact
separated 2×NO/NC
maximum load current (AC-1)
2×8 A
signaling of correct power supply
2×LED
minimum phase voltage
150 V
maximum phase voltage
280 V
effective voltage unbalance
20÷80 V
voltage hysteresis
5 V
deactivation delay on asymmetry
1÷10 s
deactivation delay in no phase
1 s
activation delay
1÷60 s
power consumption
1.6 W
working temperature
-25÷40°C
terminal
wire
2.5 mm² screw terminals
cable
2.5 mm² screw terminals
tightening torque
0.4 Nm
dimensions
1 module (18 mm)
mounting
on TH-35 rail
ingress protection
IP20
Technical data