The changeover contact of the relay allows to connect 

a visual or audible signalling system that informs abo-

ut the relay activation, which means switching off the 

motor.

power supply 

3×400 V+N

contact 

separated 2×NO/NC

maximum load current (AC-1) 

2×8 A

signaling of correct power supply 

2×LED

minimum phase voltage 

150 V

maximum phase voltage 

280 V

effective voltage unbalance 

20÷80 V

voltage hysteresis 

5 V

deactivation delay on asymmetry 

1÷10 s

deactivation delay in no phase 

1 s

activation delay 

1÷60 s

power consumption 

1.6 W

working temperature 

-25÷40°C

terminal 

wire 

2.5 mm² screw terminals

cable 

2.5 mm² screw terminals

tightening torque 

0.4 Nm

dimensions 

1 module (18 mm)

mounting 

on TH-35 rail

ingress protection 

IP20

Technical data

Summary of Contents for CKF-319 TRMS

Page 1: ...e true rms value of the voltage TrueRMS even when the power supply voltage is disturbed distorted Purpose F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48 42 227 09 71 www fif com pl e mail biuro fif com pl Donotdisposeofthisdeviceinthetrashalongwithotherwaste According to the Law on Waste electro coming from households free of charge and can give any ...

Page 2: ...ut after 1 sec The countdown to shutdown is indicated by the green diode flashing The relay is switched on again automatically when the correct network parameters return voltage hysteresis is approx 5 V If the phase sequence is changed before the sensor causing an unwanted change of the motor rotation direction the sensor will not allow the motor to start the red LED is on and the relay is off Re ...

Page 3: ... 3 Front panel ...

Page 4: ...xceeding of the voltage threshold Relay switched off voltage value of any of the phases below 150 V or above 280 V or asymmetry above the set value Incorrect phase sequence The system detected an incorrect phase rotation sequence on the input terminals Incorrect connection of neutral wire phase wire swapped with the neutral wire on the device terminals Legend green LED red LED ...

Page 5: ... 5 Legend T1 1 10 s T2 1 60 s Voltage waveforms ...

Page 6: ...es return to normal values the relay will be switched on after T2 time If a voltage asymmetry between phases occurs the relay will be switched off after T1 time The green LED R will flash until the relay is switched off time T1 If the phase voltages return to normal values the relay will be switched on after T2 time The green LED R will flash until the relay is switched switch time T2 ...

Page 7: ... 7 Legend T2 1 60 s ...

Page 8: ...will be on to indicate a phase sequence error When the correct phase sequence returns the relay will be swi tched on with a delay of T2 The green LED R will flash until the relay is switched switch time T2 If the neutral wire is connected to the wrong terminal the relay will not be switched on and the LEDs will flash in following order red green ...

Page 9: ...tor coil in series to terminals 8 9 or 11 12 6 Set the desired values using the dials 7 Switch on the power supply 8 Green LED is on correct voltage asymmetry and phase vol tage value the motor can be started 9 Red LED is on incorrect phase sequence 10 Disconnect the power supply 11 Swap the 2 phases for example L2 with L3 12 Switch on the power supply the motor can be started 13 In any other case...

Page 10: ... 10 Wiring diagram Contacts configuration ...

Page 11: ...orrect power supply 2 LED minimum phase voltage 150 V maximum phase voltage 280 V effective voltage unbalance 20 80 V voltage hysteresis 5 V deactivation delay on asymmetry 1 10 s deactivation delay in no phase 1 s activation delay 1 60 s power consumption 1 6 W working temperature 25 40 C terminal wire 2 5 mm screw terminals cable 2 5 mm screw terminals tightening torque 0 4 Nm dimensions 1 modul...

Page 12: ...i sp j declares that the device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE Declaration of Conformity along with the references to the standards in relation to which confor mity is declared can be found at www fif com pl on the product page Warranty CE declaration ...

Page 13: ...nd overvoltage circuit breakers Before connecting the power supply make sure that all cables are connected correctly It is essential to observe the operating conditions of the sensor supply voltage humidity temperature To avoid electric shock or damage to the sensor turn off the power supply whenever the connection is changed Do not make any changes to the unit yourself Doing so can re sult in dam...

Page 14: ......

Reviews: