![Falcon SSG1.5KRM-1 Owner'S Operating Manual Download Page 39](http://html.mh-extra.com/html/falcon/ssg1-5krm-1/ssg1-5krm-1_owners-operating-manual_3456720039.webp)
©
2010 Falcon
®
Electric, Inc. All rights reserved. Falcon
®
and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc.
All other brand names and trademarks are the property of their respective owners.
The information and specifications stated in this document are subject to change without notice.
08-13-2010
Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 Fax 626.962.7720
www.falconups.com - email: [email protected]
SSG Series
TM
Industrial-Grade UPS PLUS
®
1.5kVA - 3kVA
39
Model Number
SSG1.5KRM-1
SSG1.5KRM-2
SSG2.2KRM-1
SSG2.2KRM-2
SSG3KRM-1
SSG3KRM-2
Nominal VA
1500
2200
3000
Electrical Input
Nominal AC Voltage
-1 Models 120Vac
-2 Models 208-240Vac
AC Voltage Range
-1 Models 80-138Vac
-2 Models 160-276Vac
Frequency
50/60 Hz ± 5% (Auto Tracking)
Power Factor Correction
> 0.97 (at full load)
Surge Suppression
IEEE/ANSI C62.41
Efficiency (Typ.)
> 87%
Electrical Output
Watts
1050
1540
2100
AC Voltage (User Programmable)
-1 Models = 100, 110, 115 or 120Vac (sinewave)
-2 Models = 208, 220, 230 or 240Vac (sinewave)
Frequency
50/60 Hz (Auto Tracking or user programmable fixed 50 or 60Hz modes)
Frequency Stability
± 0.3% (Battery Mode), ±5% Synchronized to the input frequency in utility
mode
Voltage Regulation
± 2%
Step Load Change
± 7% for 100% load variation, recovery in 5ms
Harmonic Distortion
< 3% Linear Load, < 5% Non-Linear Load
Overload
150% for 10 seconds, 110% for 20 seconds, 105% for 50 seconds
Crest Ratio
3:1
Battery
DC Bus Voltage (nominal)
48Vdc
96Vdc
Battery Pack Type
User-Replaceable, Hot-Swappable (Batteries are replaceable through the front panel)
(Battery packs are replaceable through the front panel without removing the UPS, battery bank or EBM from the equipment rack)
Battery Type (With standard VRLA Type)
SSGLi-4 Ten-Year Lithium-Ion Battery Option
10-Year Rated, VRLA Batteries, 12Vdc, 7AH
(4) 10-Year Rated, Lithium-Ion 12Vdc, 4.6AH
10-Year Rated, Maintenance-Free, Sealed VRLA Batteries, 12Vdc, 7AH
N/A
Back Up Time (With standard VRLA Type)
SSGLi-4 Ten-Year Lithium-Ion Battery Option
SSGLi-8 2U External Lithium-Ion Bank
5 minutes / 16 minutes
9.5 minutes / 20 minutes
28.5 minutes / 60 minutes
8 minutes / 20 minutes
N/A
N/A
6 minutes / 18 minutes
N/A
N/A
Recharge Time
8 Hours to 90%
Transfer Time
Line Fails/Recovers
Zero
UPS to Bypass or Reverse
< 4ms
After Overload
Auto Transfer to UPS
With Frequency Converter Options
Bypass Disabled
Electrical Connections
Input
-1 Models = 6’ Cord with 5-15P Plug
-2 Models = 6’ Cord with Schuko Plug
-1 Models = 6’ Cord with 5-20P Plug
-2 Models = 6’ Cord with Schuko Plug
-1 Models = 6’ Cord with L5-30P Plug
-2 Models = 6’ Cord with Schuko Plug
Output
(8) 5-15R
(4) IEC320
(4) 5-15R & (1) L5-20R
(4) IEC320
(4) 5-15R & (1) L5-30R
(4) IEC320
Environmental
Temperature
Operational
Storage
-20ºC - 55ºC (-4ºF to 131ºF) (Extended operation in temperatures above 25ºC will shorten the battery life)
-15ºC - 50ºC (5ºF to 122ºF) (Extended storage in temperatures above 25ºC will shorten the battery life)
Humidity
10% to 95% Non – Condensing
Altitude
10,000 Feet (3000 meters) without derating
Cooling
Low Velocity Forced Air Fans
Heat Dissipation
(BTU/Hour)
535
784
1071
Audible Noise
(@ 1 Meter)
<50dBA
Controls & Indicators
LCD Display
MIMIC Graphical Display, Input/Output Voltage, Frequency & Load, Alarm, Programmable settings & UPS state icons
Audible Alarms
DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Over Load, Fault Alarm
Load Segment Control
Two programmable load segments, one continuous load segment
Remote Emergency Power Off (or)
Remote Output Receptacle Control
(Standard) Meets NFPA 70, NEC 645-11 (REPO connections located on the UPS rear panel)
(Optional) UPS Load Segment Controlled Output Receptacles can be turned off and on using a remote isolated switch contact.
Communications
USB Port, RS-232C Serial Port, Optional SNMP/HTTP Agent Board (UPS Bundled UPSilon 2000 Software)
Mechanical
Dimensions
inches (mm)
H x W x D
SSGH-B Battery Module
(2U) 3.5 x 19 x 21.3
(88 x 482.6 x 540)
(None - Batteries inside UPS)
(2U) 3.5 x 19 x 21.3 (88 x 482.6 x 540)
(2U) 3.5 x 19 x 21.3 (88 x 482.6 x 540)
Weight lb. (kg)
Ten-Year VRLA Batteries (Standard)
SSGLi-4 Ten-Year Lithium-Ion Battery Option
SSGLi-8 2U Lithium-Ion Extended Bank
UPS With Internal VRLA batteries = 55 (24.5)
With Internal Lithium batteries = 39.5 (17.9)
External 2U Lithium Battery Bank = 39.15
(2U) UPS Module = 32 (14.5)
(2U) External Battery Module = 70.6 (32)
N/A
N/A
(2U) UPS Module = 32 (14.5)
(2U) External Battery Module = 70.6 (32)
N/A
N/A
Agency Approvals
-1 Models = UL 1778, CUL, FCC Class B, -2 Models = CE, UL 1778, CUL