MODEL

kW (net) Btu/hr (gross)

G350/9

9.6

36,000

G350/10

19.2

72,000

BURNER

NATURAL

PROPANE

MAIN

ù2.9

Amal 390

PILOT

N 16

LP 10

SECTION 1 - INSTALLATION

1.2 SITING
The appliance should be installed on a level, fireproof

surface in a well lit and draught free position.
Should the floor be of combustible material, then local

fire requirements should be checked to ensure

compliance. A clearance of 150mm should be left

between the back and sides of the appliance and any

combustible wall. There should be a minimum vertical

clearance of 1650mm above top edge of chargrill flue.
The chargrill rear becomes VERY HOT. If installed in

a free-standing position, appliance rear MUST BE

GUARDED to protect operators against burns.
Important
If the appliance is to be installed in a suite formation

with matching appliances then the instructional

literature for these should be consulted in order to

determine the necessary clearances to any

combustible rear wall or overlying surface(s). Some

units require greater clearances than others.

The largest figure quoted in the individual instructions

will therefore determine the clearance of the complete

suite adjoining appliances.

1.3 VENTILATION
Adequate ventilation, whether natural or mechanical,

must be provided to supply sufficient fresh air for

combustion and allow easy removal of combustion

products which may be harmful to health.

Recommendations for Ventilation of Catering

Appliances are given in BS5440 : 2. Furthermore,

to ensure sufficient roomventilation, guidance on the

volume of ventilation air required for different types of

catering equipment is provided in the table.

For multiple installations the requirements for

individual appliances should be added together.

Installation should be made in accordance with local

and/or national regulations applying at the time.

A competent installer MUST be employed.

1.4 GAS SUPPLY
The incoming service must be of sufficient size to

supply full heat without excessive pressure drop.

A gas meter will be installed in the system by Gas

Supplier. Any existing meter should be checked,

preferably by Gas Supplier to ensure that it is of

adequate capacity to supply the entire installation.

This is, of course, particularly important when a

number of units, (i.e. a "suite" is being installed.)
Installation pipework must be fitted in accordance

with IGE/ UP/ 2.
The size of pipework supplying the appliance must be

not less than the inlet connection (R

1

/

2

,

1

/

2

" BSP).

An isolating cock must be located close to the

appliance to allow shut down during an emergency

or routine servicing.
After installation, the complete installation must be

checked for gas tightness: see IGE/ UP/ 1.

1.5 ELECTRICAL SUPPLY
Not applicable to these appliances.

1.6 WATER SUPPLY
Not applicable to these appliances.

1.7 TOTAL RATED HEAT INPUTS -

NATURAL and PROPANE GAS

1.8 INJECTOR SIZE -

NATURAL and PROPANE GAS

EQUIPMENT

Ventilation Rate Required

m

3

/ min

ft

3

/min

Range, Unit Type

17

600

Pastry Oven

17

600

Fryer

26

900

Grill

17

600

Steak Grill

26

900

Boiling Pan

17

600

Steamer

17

600

Sterilizing Sink

14

500

Bains Marie

11

400

Tea/ Coffee Machine

8.5 - 14

300 - 500

UNLESS OTHERWISE STATED, PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER

ARE NOT TO BE ADJUSTED BY THE INSTALLER

MODEL

WIDTH

mm

DEPTH

mm

HEIGHT

mm

WEIGHT

kg

WEIGHT

lbs

G350/9

350

650

305

46

101

G350/10

700

650

305

78

172

1.1 MODEL NUMBERS, NETT WEIGHTS