1.8 INJECTOR SIZE

 

1.8.1 Natural Gas

 

 

Model

 

Pilot Burner

 

Cross-lighter

 

Main Burner

 

G1808X

 

    51

 

0.026

 

2 x Ø2.38mm

 

G1838X

 

    51

 

0.026

 

2 x Ø3.3mm

 

G1848X

 

    51

 

0.026

 

4 x Ø2.38mm

 

 

1.8.2 Propane Gas

 

 

Model

 

Pilot Burner

 

Cross-lighter

 

Main Burner

 

G1808X

 

    35

 

0.016

 

2 x Ø1.47mm

 

G1838X

 

    35

 

0.016

 

2 x Ø1.95mm

 

G1848X

 

    35

 

0.016

 

4 x Ø1.47mm

 

 

 

1.9 GAS PRESSURE ADJUSTMENT

 

1.9.1 Supply Pressures

 

A pressure test point is fitted on the burner manifold and 

the  operating  pressure  is  shown  in  the  tables  below. 

On  G1848X  model,  burner  pressure  should  be  set 

with  both pans turned on.

 

An  adjustable  governor  is  required  on  Natural  Gas 

models.

 

 

Gas type

 

mbar

 

inches w.g

 

Natural Gas

 

20

 

8

 

Propane Gas

 

37

 

14.8

 

 

 

1.9.2 Natural Gas Burner Pressures

 

 

Model

 

mbar

 

inches w.g.

 

G1808X

 

13

 

5.2

 

G1838X

 

11.2

 

4.48

 

G1848X

 

13

 

5.2

 

 

1.9.3 Propane Gas Burner Pressures

 

 

Model

 

mbar

 

inches w.g.

 

G1808X

 

35.6

 

14.2

 

G1838X

 

34.5

 

13.8

 

G1848X

 

35.6

 

14.2

 

 

 

1.10 BURNER ADJUSTMENTS

 

1.10.1 Pilot

 

No adjustment is available.

 

Main Burner

 

No  aeration  adjustment  is  necessary,  however  gas 

pressure should be set as per value shown in Section 1.9.

 

SECTION 2 -

 

ASSEMBLY and COMMISSIONING

 

 

2.1 ASSEMBLY

 

The unit is packed as a complete assembly.

 

 

2.2 APPLIANCES ON CASTORS

 

For  units  on  castors,  refer  to  guidelines  in  BS6173. 

These  state  that  where  wheels,  castors  or  rollers  are 

used, these must be fitted with a brake or locking device. 

This should be accessible to operator from front or side.

 

 

2.3 CONNECTION TO A GAS SUPPLY

 

Gas supply piping and unit connection must be installed 

in accordance with regulations listed on front page of this 

document.

 

A gas  isolating  cock  must  be  fitted  to  the  supply  in  a 

position that is readily accessible to operator.

 

 

2.4 CONNECTION TO AN ELECTRICAL SUPPLY

 

Not applicable to these units.

 

 

 

2.5 CONNECTION TO A WATER SUPPLY

 

Not applicable to these units.

 

 

 

2.6 PRE-COMMISSIONING CHECK

 

Prior to operation, ensure that all packing material has 

been removed from unit.

 

2.6.1 Setting The Gas Pressure

 

a)  It  is  necessary  to  check  gas  pressure  during 

commissioning.  A suitable  pressure  gauge  must  be 

connected to test point on supply manifold.

 

b) Turn on main gas valve at supply.

 

c)  Light  burners  as  detailed  in  User    Instructions. 

The  supply pipes may contain air therefore it may be 

necessary to repeat lighting procedure.

 

d) 

Natural gas models only

. Adjust governor to setting 

as detailed in Section 1.9.

 

e)  Disconnect pressure gauge from test point.  Replace 

sealing screw and test gas soundness.

 

 

2.7 INSTRUCTION TO USER

 

After  installing  and  commissioning  the  fryer,  hand  User 

Instructions  to  operator  or  purchaser.  Ensure  details  to 

light,  turn  off,  use  and  clean  are  properly  understood. 

The  main  gas  isolating  valve  location  should  be  made 

known to user and the procedure for operation in event of 

an emergency should be demonstrated.

 