Modbus Communications
A.3. RTU
Framing
The example below shows a typical Query/Response from an Wireless Gateway.
Slave address 2 responds to Function Code 4 with six bytes of hexadecimal data and ends with
CRC16 checksum.
Register Values:
40001 = 0000 (hex)
40002 = 0000 (hex)
40003 = 0001 (hex)
Register
Name
Description
Units
Range
40001
Id
Sensor Identification number
uint16
0-65535
40002
Out Of Service
Shows when the sensor is in
maintenance mode or offline
uint16
0-65535
40003
Serial #
Wireless sensor serial number uint16x4
0-65535
40007
Raw Data #1
First data value displayed by
sensor
Unsigned 32 bit
integer
0-4294967295
40009
Raw Data #2
Second data value displayed
by sensor
Unsigned 32 bit
integer
0-4294967295
40011
Raw Data #3
Third data value displayed by
sensor
Unsigned 32 bit
integer
0-4294967295
40013
Converted Data #1
First data value converted by
the Wireless Gateway
Unsigned 32 bit
integer
0-4294967295
40015
Converted Data #2
Second data value converted
by the Wireless Gateway
Unsigned 32 bit
integer
0-4294967295
40017
Converted Data #3
Third data value converted by
the Wireless Gateway
Unsigned 32 bit
integer
0-4294967295
40019
Age
Time since last transmission
received
Unsigned 32 bit
integer
0-4294967295
48001
Offline Delay
Time till the sensor reads
offline
uint16
0-65535
Table A.3
Output Registers
Slave
Address
Function
Code
Count Bytes
of Data
Register
Data
Msb Lsb
Register
Data
Msb Lsb
Register
Data
Msb Lsb
CRC 16
“Lsb”
CRC 16
“Msb”
02
04
06
00 00 00 00 00 01 B5
A3
Table A.4
Response Sample
Summary of Contents for FDS-Wi
Page 1: ...Monitoring User Guide FDS Wi Wireless Gateway Version 2 4...
Page 60: ...www rletech com 60 970 484 6510 4 Web Interface Integration Version...
Page 66: ...www rletech com 66 970 484 6510 A Modbus Communications...
Page 70: ...www rletech com 70 970 484 6510 B Troubleshooting...
Page 76: ...970 484 6510 76 rletech com...