2.5.2 REPLACEMENT OF PILOT BURNER INJECTORS
The pilot burner injector is accessed by removing the lower front panel. Remove the side
and lower screws.
The pilot burner is in the front of the combustion chamber.
Undo the screw and replace the injector with an appropriate one.
2.5.3 MINIMUM OUTPUT ADJUSTMENT
When appliance has been switched on, set control to minimum position.
Remove control knob to reveal a small hole on the panel of the appliance.
Turn the minimum adjustment screw on the control with a screwdriver through the hole on
the panel.
Warning! Measure the minimum output pressure directly at the output pressure connection
on the injector tube (see figure “Measuring gas pressure”)
Set the output pressure of the gas cock according to the figures stated in table 4 - Minimum
output setting).
After setting, seal the adjustment screw!
Warning!
After each conversion, it is necessary to check tightness and operation!
2.6 MAINTENANCE
Warning!
All maintenance operations shall only be performed by a technically qualified
service centre!
To ensure correct and safe operation, the appliance must be inspected and serviced at least
once a year only. Maintenance includes also to control the components and tear of pipes,
feeding pipes etc.
It is advisable to replace worn components during maintenance operations to avoid the need
for other maintenance calls and unexpected failures.
It is also advisable to apply for a maintenance contract with the customer.