4
MAN-AGY-005. Version 01 (01/11/2017)
For multiple base units connected to the keypad, the use of SGY-011, CBL-036 and
CBL-035 (terminator) is highly recommended. See diagram below.
Operation
Once connected to the agility
TM
host unit/s, menu structures and programming are the
same as detailed in the agility
TM
manuals MAN-AGY-001 and MAN-AGY-002 (both may
be downloaded from www.fairford.co.uk).
However, specific steps must be taken to connect the Remote Keypad to one or more
agility
TM
host units.
Initial Power-Up
If the host agility
TM
unit/s and the remote keypad have the default Modbus transmission
parameters set,
and the host unit is powered and has Keypad power set to ‘on’, the
keypad will automatically communicate with the host. The following status screen will
be seen:
Connection and Operation (continued)
SGY-011
Close Jumper S6
(supplies power to AGY-010)
CBL-036
CBL-035
(last unit only)
Enable keypad
power
on this unit
only
Status of connected host
Control method
(Local, Remote, Modbus)
Modbus address
of connected unit
Navigation Wizard
(displays ‘active’ keys)
Motor Overload level
The agility
TM
units must have: a unique Modbus address on each unit and identical
Parity/Baud rate values on each unit
Address = 1
Address = 2
Address = 3