Installation
Page 20/55
5
Installation
5.1
Installation and safety instructions
For the installation and maintenance of the sensors, the requirements of the Explo-
sion Protection Regulations, the Industrial Health and Safety Regulations and the
Equipment Safety Regulations as well as generally accepted rules of engineering
and this manual must be observed.
All applicable local safety and accident prevention regulations not included in this
manual must also be observed.
During the assembly, it is important to make sure that the probe tube is not bent.
Protect the floats from knocks at all times. No moisture may enter the M12 con-
nector.
Before installation move the supplied floats to the bottom end of the probe tube,
otherwise they will slip down suddenly when you erect the sensors and could be
damaged when striking the circlip.
During the installation, following data of the VISY-Stick sensors, tanks, and prod-
ucts are to be noted for configuring the VISY-Command:
- Device numbers of the sensors,
- Tank assignments of the sensors,
- Tank assignments of the products,
- Terminal connection of the sensors in the VISY-Command,
- Sensor distances from the central vertical axes of the tanks (see Chapter 5.4)
For identification purposes, the probe heads of the various model types are
wrapped in a coloured net, which must be removed prior to installation. The
probes are associated with the following colours:
VISY-Stick N for AdBlue®:
blue
VISY-Stick Interstitial:
brown
VISY-Stick LPG:
yellow
VISY-Stick Biodiesel:
green
VISY-Stick Ethanol (>15%):
orange
VISY-Stick E15 (0-15 %):
white
VISY-Stick / Advanced / Flex / VISY-Reed / VISY-Sump
without net