background image

 

Page 1/3 

 

FAFNIR GmbH 

  Schnackenburgallee 149 c 

  22525 Hamburg 

  Tel.: +49 / (0)40 / 39 82 07-0 

  www.fafnir.de 

  [email protected] 

 

 

Instructions in accordance with directive 2014/34/EU

 

TÜV 00 ATEX 1656

 

Overfill Prevention Sensor type 81 D-Ex 

 and 83 UV-

 

Level Detector type LS 300 

 

High-Level Sensor type SEPARIX-T 

 

Stand: 09.2018 

Range of application 

The sensors are intrinsically safe operating equipment for use in explosion hazardous area and serve for 
detecting the limit level. The overfill prevention sensors serve as part of a overfill prevention device. The 
level detector is used as part of an overfill protection device, dry run protection or filling control. The 
high-level sensor is used to detect a fluid back pressure within a light liquid separator. 

II 

Standards 

The sensors are designed in accordance with the following European standards 

EN 60079-0:2012 + A11:2013 

Equipment 

 General requirements 

EN 60079-11:2012 

Equipment protection by intrinsic safety "i" 

EN 60079-26:2015 

Equipment with Equipment Protection Level (EPL) Ga 

III 

Instructions 

for safe …

 

III.a 

… 

use 

The sensors are designed as intrinsically safe equipment and are suitable for use in potentially explosive 
areas. The level detectors LS 300 

 C (coated with plastic) are suitable for the gas groups IIA and IIB. All 

other level detectors are suitable for all gas groups (IIA, IIB and IIC). 
The approval applies to device versions 81 D-Ex 

…, 83

 UV-

…, LS

 300 

… and SEPARIX

-T 

 

III.b 

… 

assembling and dismantling 

Assembling and dismantling must solely be carried out with the power disconnected! 
For  sensors  with  connection  housing  the  cover  of  the  connection  housing  may  be  removed  for  the 
electrical installation. After installation, the connection housing must be locked again. 

III.c 

… 

installation 

The wiring must be carried out only with the power disconnected. Special rules and regulations, includ-
ing EN 60079-14 and local installation regulations, must be observed. 
The sensors can be installed completely inside Zone 0. If the integrated overvoltage protection is used, 
e.

g. LS 300 U, the terminal compartment with overvoltage protection must be installed outside Zone 0. 

General information (see also EN 60079-14:2014, Clause 16.3 or EN 60079-25:2010, Clause 12): 

The overvoltage protection device must be installed outside, but as close to the border of Zone 0 as 
technically possible, preferably at a distance of up to 1 m. 

If a screw-in unit is used, it must be provided with a suitable sealing material and screwed into the tank 
coupling. If the sensor tube is permanently connected with a flange, the installation length cannot be 
changed. The flange shall be provided with a suitable seal and fixed with flange bolts or nuts. 
By the process connection, there may be an opening in the boundary wall to the area requiring EPL "Ga". 
Then, there is the risk of flammable gases release and flame entrance. 
If the sensor is supplied without process connection, the installer is responsible for compliance with the 
EX requirements. 
General information (see also EN 60079-26, Clause 4.3): 

Attention must be paid, if the sensor is installed in the separating wall between Zone 0 and Zone 1. 
Then a protection class of at least IP66 or IP67 must be achieved after installation. 

 

 

Reviews: