Technical data 

The following electrical input values apply to the sensors: 

U

i

 

 

30 V 

I

i

 

  200 mA 

P

i

 

 

1 W 

The effective internal capacitance and inductance that are externally effective, are negligibly small. If the 
sensors are supplied with integrated cable, then the electrical characteristics are: 

C

c

  =  200 

pF

/

m

 

L

c

  = 

µH

/

m

 

L

c

/R

c

 = 

30 

µH

/

Ω

 

The sensors may be used in the following ambient temperature range: 

T

a

  =  -40 °C 

… +110

 °C 

When using a sensor with overvoltage protection, the maximum temperature is +90 °C for the sensor 
head. 
General remark (see also EN 60079-0, Clause 1): 

Zone 0 is given only under atmospheric conditions: 
  Temperature range: 

-20 °C 

 +60 °C 

  Pressure range: 

0,8 bar 

 1,1 bar 

  Oxidant: 

Air (oxygen content approx. 21 %) 

The sensors achieves a degree of protection of: 

degree of protection: 

IP68 

The following technical data apply to sensors with overvoltage protection: 
The nominal DC spark-over voltage amounts to: 

U  =  350 V ± 20 % 

The nominal impulse discharge current amounts to: 

=  20 kA (10 × Wave 8/20 

μs)

 

The nominal alternating discharge current amounts to: 

=  20 A (10 × @ 50 Hz, 1 s) 

The insulation resistance of an overvoltage arrester amounts to: 

R  >  10 

 

VI 

Special conditions of use 

1.

 

Overfill Prevention Sensor and Level detectors with overvoltage protection do not comply with the 
dielectric strength requirements according to EN 60079-11, Clause 6.3.13. When performing an in-
sulation test of the intrinsically safe circuit it is therefore necessary to disconnect the device. 

2.

 

When using the integrated overvoltage protection, integration into the equipotential bonding is re-
quired. 