FACTORY PARAMETERS MENU
To access the factory parameters menu, down into the working parameters menu (page
11) until "PIN0000", press
, enter the number 0023 through the key
, press
to
save.
Caution
: When entering this menu, all the analogic outputs of the device will be closed and the adjusting operation
will be stopped until the menu is closed.
B
ASIC
S
ETTINGS
Allows to load one of the settings based on the below tables. Select one setting to speed
the programming up (Default = mp 420_50).
Then the signle parameters can be modified anyway.
Caution:
previous settings will be overwritten; as for the Master pre-settings the values of SPD1 and SPD2 will be of
20% and 90% respectively.
COOL
HEAT
CHILLER
2
Input
type
Scale
P1
P2
MaxP
P1
P2
MaxP
mpRZM_20
0,5..4,5V
0..20,7 bar 8 bar
12 bar
13 bar
4 bar
6 bar
3 bar
MPRZM_34
0,5..4,5V
0..34,5 bar 13 bar
18 bar
19 bar
4 bar
6 bar
3 bar
MPRZM_45
0,5..4,5V
0..45 bar
20 bar
24 bar
25 bar
7 bar
11 bar
5 bar
MP420_30
4..20 mA
0..30 bar
13 bar
18 bar
19 bar
4 bar
6 bar
3 bar
MP420_50
4..20 mA
0..50 bar
20 bar
24 bar
25 bar
7 bar
11 bar
5 bar
COOL
HEAT
DRY COOLER
Input type
T1
T2
MaxT
T1
T2
MaxT
MTNTC_L
10kΩ @ 25°C (β3435)
22°C
28°C
29°C
22°C
24°C
21°C
MTNTC_H
10kΩ @ 25°C (β3435)
38°C
45°C
46°C
22°C
24°C
21°C
SLAVE
2
Input type
IN. MIN.
IN. MAX
V1
V2
S0_10
0..10V /Pwm
13%
95%
20%
100%
S4_20
4..20mA
13%
95%
20%
100%
S_PWM FV
Pwm FV
For Slave mode command with Modbus, see the Modbus settings menu (page 24).
Allows to select the motor adjusting curve.
Possible modes:
Q
= optimized for fans (Def.),
L
= linear
Allows to forbid the access to the “Operating parameters” menu.
ON (Def.): allows the access
OFF: forbids the access
0000
PIN
[PW]
PRESET.
[IB]
Q
[IB]
*
REG. MODE
ON
[IB]
*
USER ACTIV