page 16

ON

OFF

1 2 3 4 5 6 7 8 9 10 11 12

DIP-SWITCH - A 

meccanica

FADINI

X

FOR

 SWINGING GATE OPENERS:

position Dip Switch B No.1= OFF

2 3 4

1

ON

OFF

DIP-SWITCH - B 

1 2

1 2 3 4

ON

OFF

DIP-SWITCH - B 

Limit Switches: 

if not 

fitted, link out the 

terminals or use 

terminals 9 and 10 for 

the function 

reverse 

direction during 

opening

 (described on 

page 18) (*)

 if the limit switches 

then bridge inputs 8 and 10 with common 9 .

The terminals 9 and 10 also provide inputs 
for the NC contact on opening: if activated 
during the opening cycle, gate travel is 
reversed for a short distance  (see 
paragraph Functions on page 18)

12 13

GB

UNIVERSAL ELECTRONIC CONTROL BOXES 

230V 50/60Hz SINGLE-PHASE 

 Photocells stop gate during opening

 Radio does not reverse in opening

 Automatic closure 

Pre-flashing operational

 Step-by-step radio

 Pedestrian service

 Stroke Reversing Pulse on Opening

 No wing delay during opening.  Motors start  together

 Enables input of the 2nd pair of photocells 

 Flashing light off during pause

 Re-closes in Opening and  Dwell time after crossing the 

photocells 

 Memory of time settings when frequent operations 

are needed   

 

 mode

 Deadman function

 reverse direction by means of the safety devices in the operation area

 DSA control of the photocell transmitters if conneced to the dedicated terminals

Dip-Switches and LED signals of the various functions

Accessory

Electrical connections

2nd pair of 

Photocells:  

installed internally

With 

 The gates 

stay stopped as long as the photocells are obstructed.
- In opening cycle: obstacle removed, gates go on opening 
- In closing cycle: obstacle removed, gate travel reversed

max. load:

n°1 radio receiver 

n°2 pairs photocells

DIP-SWITCH-A N°9:

 Photocell 2nd pair enabled

  No  photocell 2nd pair used

9

L2 

= no obstacle present, turns off with 

obstacle present

1° pair Photocells:  

installed externally

1

DIP-SWITCH-A N° 1:

ON

: stop gate in opening and reverse in

       closing when cleared 

OFF

: no stop in opening and reverse in

         closing  when obstructed 

All NC contacts of 
safety accessories 
such as Photocells 
(receivers) must be 
connected in series 
with terminals 1 and 2      

NC

NC

1 2

L3 ON

= no obstacle.  It goes off in case

              of obstacle

12 13

Radio contact 
(step-by-step mode):

ON

:

during opening does not reverse and does 

not stop

 

OFF

during opening always stop and reverses

2

ON

:

Step-by-step with intermediate stop

OFF

:

 Reverses movement by  radio impulse

 

5

DIP-SWITCH-A N°2 and N°5:

3

7

L7 OFF= 

no RADIO contact, turns on with 

every radio contact impulse

Key-operated 
switch

3 4 5 6

NC

L4 OFF=

 no OPEN contact, turns on with 

every open impulse

L5 OFF=

 

 no CLOSE contact, turns on with 

every close impulse

NO and NC contacts to connect to the 

respective  terminals  on  the  selector 

switches or the push-button panel.

All possible configurations are attached 

to the related control accessories.

L6 ON=

 

 STOP contact closed, turns off with 

every stop impulse

L8 ON

off when gate closed

L9 ON

off with gate open

8 9 10

connecting any NO contact across the two 
terminals generates, with each impulse:
- Opening only:  
- inversion of direction with each impulse 

- Step-by-step:  Open-Stop-Close-Stop 

- During opening no new command is 
accepted. During dwell or closing, each new 
command stops and reverses travel 
direction.

  

n°1 radio receiver 

n°2 pairs photocells

XE

Summary of Contents for Elpro X

Page 1: ...ators fitted with mechanical clutch and pressure valve adjustment equipped with electric torque control designed for electro mechanical operators without mechanical clutch PROGRAMMATEURS ELECTRONIQUES...

Page 2: ...RE VERSIONE 03 ON OFF 1 2 3 4 5 6 7 8 9 10 11 12 DIP SWITCH A MORSETTIERA PER IL COLLEGAMENTO DEI LED DELLA PULSANTIERA 1 2 3 4 5 6 7 8 9 10 11 1213 14 15 16 1718 19 20 21 22 23 24 25 28 26 27 USCITA...

Page 3: ...stop L7 Spento nessun contatto RADIO si accende ad ogni impulso del contatto radio Fotocellula ferma in apertura Radio non inverte in apertura Chiude in automatico Prelampeggio Attivo Radio passo pass...

Page 4: ...arie funzioni 18 16 17 M1 16 1718 C1 Condensatore Motore M1 C1 Condensatore Motore M1 Lampeggiante 230V 23 22 DIP SWITCH A N 4 e N 10 ON Prelampeggio prima dell apertura OFF Senza prelampeggio 4 ON La...

Page 5: ...utotenuta nei Rel quindi l attiva presenza dell operatore durante tutto il movimento dell automazione fino al rilascio del pulsante o della chiave del selettore 2 ON Attiva funzione Uomo Presente OFF...

Page 6: ...voro modalita Uomo presente inversione di marcia con dispositivi di protezione dell area di apertura controllo DSA fotocellule trasmettitori se collegati ai morsetti dedicati 2 coppia di Fotocellule i...

Page 7: ...I TEMPO DI APRE CHIUDE 12 13 Uscita per una eventuale lampada di segnalazione 24V max 3W dello stato dell automazione Spia Cancello Aperto Spia Cancello Chiuso Lampeggia movimento di chiusura Lampeggi...

Page 8: ...2 coppia fotocellule non utilizzata 9 16 15 Funzione che permette di facilitare il disimpegno dell Elettroserratura a cancello completamente chiuso anche in modalita Apertura Pedonale le ante del can...

Page 9: ...otocellule ricevitori devono essere collegati in serie ai morsetti 1 e 2 3 4 5 6 NC 3 7 L3 Acceso nessun ostacolo presente si spegne ad ostacolo presente L4 Spento nessun contatto APRE si accende ad o...

Page 10: ...accio e Lampeggiante 230V 23 22 DIP SWITCH A N 4 e N 10 ON Prelampeggio prima dell apertura OFF senza prelampeggio 4 ON Disattivato durante la pausa in Funzionamento Automatico con Dip 3 ON OFF Alimen...

Page 11: ...la coppia fotocellule dopo 3 secondi OFF Nessuna richiusura automatica 16 15 Funzione per utilizzi altamente intensivi con frequenti inversioni di marcia questa funzione abilitata tiene conto del temp...

Page 12: ...processo 230V grid voltage Present and fuses F1 F2 F3 F4 only for Elpro X 2nd pair of Photocells or Safety Edge no obstacle present 1st pair of Photocells no obstacle detected Open turns on with open...

Page 13: ...cycles and gate stopping with DIP SWITCH A N 8 and N 9 Increase time during inversion No increase of inversion time 8 Inversion of direction with safety edge No inversion of direction 9 Limit switches...

Page 14: ...eration OFF Flashing during the pause during Automatic Operation 10 230V Control box power supply 24 25 24 25 12 13 Connections to Pulin 3 erminal board for connecting the push button panel Leds 26 27...

Page 15: ...P SWITCH A N 3 3 4 16 15 FUNCTIONS FOR SLIDING GATE OPENING Dip Switch B n 1 ON meccanica FADINI X UNIVERSAL ELECTRONIC CONTROL BOX 230V 50 60Hz SINGLE PHASE GB with one impulse from the open command...

Page 16: ...moved gates go on opening In closing cycle obstacle removed gate travel reversed max load n 1 radio receiver n 2 pairs photocells DIP SWITCH A N 9 Photocell 2nd pair enabled No photocell 2nd pair used...

Page 17: ...lamp Output max 3W 3 11 12 13 24V ac OUTPUT for max load No 2 pairs of photocells No 1 radio receiver No 1 LED Chis 37 Chis E37 Keyswitch All instructions are attached to the related control accessori...

Page 18: ...rst opening command opens the M1 gate for pedestrians A second opening pulse will operate the gate fully open along with the other gate M2 motor The function Pedestrian Opening is not in service durin...

Page 19: ...vel in opening and reverse in closing once cleared from obstacle OFF no stop in opening and reverse in closing in case of obstacle All NC contacts of safety accessories such as Photocells receivers mu...

Page 20: ...tput max 3W 3 11 12 13 24V AC OUTPUT for max load No 2 pairs of photocells No 1 radio receiver No 1 LED Chis 37 Chis E37 key switch All instructions are attached to the related control accessories Sin...

Page 21: ...memory enabled OFF No memory enabled 4 ON Activates the DSA safety control OFF Deactivates the DSA safety control DIP SWITCH B N 4 16 15 For the control evice for afety uto test it is necessary to co...

Page 22: ...TEUR MICROPROCESSEUR VERSION 03 ON OFF 1 2 3 4 5 6 7 8 9 10 11 12 DIP SWITCH A BORNIER POUR LE RACCORDEMENT DES LEDS DE LA BOITE A BOUTONS POUSSOIRS 1 2 3 4 5 6 7 8 9 10 11 1213 14 15 16 1718 19 20 21...

Page 23: ...t chaque impulsion d arr t L7 Eteinte aucun contact RADIO elle s allume chaque impulsion du contact radio Photocellule arr te l ouverture Radio n inverse pas l ouverture Ferme en automatique Pr cligno...

Page 24: ...es fonctions 18 16 17 M1 16 1718 C1 Condensateu r Moteur M1 C1 Condensateur Moteur M1 Lampe clignotante 230V 23 22 DIP SWITCH A N 4 et N 10 ON Pr clignotement avant l ouverture OFF Sans pr clignotemen...

Page 25: ...ans autotenue dans les Relais donc il y a la pr sence active d un op rateur pendant tout le mouvement de l automation jusqu la rel che de la touche ou de la cl du s lecteur 2 ON Active la fonction Hom...

Page 26: ...travail modalit Homme mort inversion de marche avec dispositifs de protection de la partie d ouverture contr le DSA projecteurs photocellules si raccord s aux bornes d di es 2 me paire Photocellules i...

Page 27: ...MPS DE TEMPS DE OUVRE FERME 12 13 Sortie pour un ventuel voyant de signalisation 24V max 3W de l tat de l automation Voyant Portail Ouvert Voyant Portail Ferm Clignote mouvement de fermeture Clignote...

Page 28: ...ellules OFF 2 me paire photocellules pas utilis e 9 16 15 Fonction qui facilite le d gagement de la serrure lectrique quand le portail est compl tement ferm m me en modalit d Ouverture Pi tonne les va...

Page 29: ...lules r cepteurs doivent tre raccord s en s rie aux bornes 1 et 2 3 4 5 6 NF 3 7 L3 Allum e aucun obstacle elle s teint en pr sence de l obstacle L4 Eteinte aucun contact OUVRE elle s allume chaque im...

Page 30: ...ique Lampe clignotante 230V 23 22 DIP SWITCH A N 4 et N 10 ON Pr clignotement avant l ouverture OFF Sans pr clignotement 4 ON D sactiv pendant la pause en Fonctionnement Automatique avec Dip 3 ON OFF...

Page 31: ...4 IMPORTANT utiliser toujours et seulement avec le Dip A N 3 ON X PROGRAMMATEURS ELECTRONIQUES UNIVERSELS 230V 50 60Hz MONOPHASE XE X Pour le contr le ispositif curit utotest il faut raccorder cette s...

Page 32: ...OR MICROPROCESOR VERSI N 03 ON OFF 1 2 3 4 5 6 7 8 9 10 11 12 DIP SWITCH A BORNERA PARA LA CONEXION DE LOS LED DEL TABLERO 1 2 3 4 5 6 7 8 9 10 11 1213 14 15 16 1718 19 20 21 22 23 24 25 28 26 27 SALI...

Page 33: ...e stop L7 Apagado ning n contacto RADIO se enciende cada impulso de contacto radio Fotoc lula parada en abertura Radio no invierte en abertura Cierre en autom tico Prelampeo activo Radio paso paso Ser...

Page 34: ...varias funci nes 18 16 17 M1 16 1718 C1 Condensador Motor M1 C1 Condensador Motor M1 Destellador 230V 23 22 DIP SWITCH A N 4 y N 10 ON Pre relampeguo ante de la abertura OFF Sin pre lampeguo 4 ON Des...

Page 35: ...enuda sin auto capacidad en los Rel s por lo tanto la activa presencia del operador durante el movimiento de la automaci n hasta la liberaci n del pulsador o de la llave del selector 2 ON Activa funci...

Page 36: ...ansmisor si conectados con los bornes 2 parejas de Fotoc lulas instaladas interiormente 1 2 DIP SWITCH A N 9 ON Habilita la 2 parejas de fotoc lulas OFF 2 parejas de fotoc lulas no utilizada 9 1 2 3 4...

Page 37: ...do de la automaci n Espia Verja Abierta Espia Verja Parada Relampagueo movimiento de cierre Relampagueo movimiento de abertura Electrocerradura 14 15 Salida alimentaci n 12 Vac por 15 VA max L electro...

Page 38: ...mite de facilitar la salida de la electrocerradura a verja completamente abierta tambi n en modalidad Abertura Peatonal las hojas de la verja cerrada antes de la abertura se insertan en el cierre para...

Page 39: ...ad obstaculo presente L4 Apagado ning n contacto ABRE se enciende cada impulso de abertura L5 Apagado ning n contacto CIERRE se enciende cada impulso de cierre L6 Encendido contaco de STOP cerrado se...

Page 40: ...PO DE TIEMPO DE ABRE CIERRE 12 13 Electrocerradura 14 15 Salida alimentaci n 12Vac para 15VA max 18 21 16 19 17 20 M1 16 1718 19 20 21 M2 C2 Condensador Motor M2 Alimentaci n Pulin 3 26 27 28 28 26 27...

Page 41: ...ctar a esta salida y seleccionar el ante de cada movimiento de la verja se esta funci n est habilidada el Elpro X y el Elpro XE comproban que todos los dispositivos fotoc lulas conectados est n libre...

Page 42: ......

Page 43: ......

Page 44: ...arried out by qualified technicians following Meccanica Fadini s Safety Norms Manual L installation doit tre effectu e par un technicien qualifi suivant le manuel des Normes de S curit de Meccanica Fa...

Reviews: