SUPPORTING LADDER LOGIC
3.2
ALARM WORD DECODING
The rung below copies the alarm bits for loop 1 (V5004) into Y0-Y4.
Y0
Temperature Low Alarm
Y1
Temperature High Alarm
Y2
Temperature Deviation Limit Alarm
Y3
Broken RTD or Thermocouple (Burn-out detected)
Y4
No Heater Current Alarm (open or disconnected)
ALARM WORD ENCODING
Some operator interface software packages do not permit examining discrete bits in user V-Memory.
The following example converts the bits in the Alarm Word into a corresponding BCD number.
If more than one alarm is on then the BCD number for the least significant bit in the Alarm Word will be
returned. Thus a "Low Temperature Alarm" will override a "Temperature Deviation Alarm". A "Broken
Transmitter Alarm" will always be recognized since in this case the Temperature Controller disables all
other alarms and loop processing.
Alarm Word
Encoded BCD Number
Bit Number
Description
1
0
Temperature Low Alarm
2
1
Temperature High Alarm
3
2
Temperature Deviation Limit Alarm
4
3
Broken RTD or Thermocouple (Burn-out detected)
5
4
No Heater Current Alarm (open or disconnected)
6
5
No Heater Current Control Alarm (output shorted)
Load Alarm Word for Loop 1 to accumlator
Shift bits 1 position to the left for ENCODE
Position of 1st bit is put in accumulator
Summary of Contents for Direct Logic 405
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 16: ...INTRODUCTION 1 6...
Page 38: ...INSTALLATION AND WIRING 2 22...
Page 45: ...SUPPORTING LADDER LOGIC 3 7...
Page 47: ...SUPPORTING LADDER LOGIC 3 9...
Page 48: ...SUPPORTING LADDER LOGIC 3 10...
Page 62: ...TROUBLESHOOTING 6 4...