INSTALLATION AND WIRING
2.12
TEMPERATURE CONTROLLER LOOP CONFIGURATION MEMORY MAP, 1 LOOP
Decimal Offset
Example V-Mem.
Description
Units
0-1 Read continually
0
V5000
Mode Word
bit mapped
1
V5001
Temperature Setpoint
± 3276.7
E
C/
E
F
2
V5002
Output Bias
0.0-100.0% or 0-4095
3-5, Written after each temperature acquisition
3
V5003
Output
0.0-100.0% or 0-4095
4
V5004
Alarm Word
bit mapped
5
V5005
Process Temperature
± 3276.7
E
C/
E
F
6-8, Read if Mode Word bit 0 is set (Written by Controller after Auto Tune completion)
6
V5006
Gain (Proportional)
0.0-6553.5
7
V5007
Reset (Integral)
0-65535 seconds
8
V5010
Rate (Derivative)
0-65535 seconds
9-23, Read if Mode Word bit 0 is set
9
V5011
Low Alarm
± 3276.7
E
C/
E
F
10
V5012
High Alarm
± 3276.7
E
C/
E
F
11
V5013
Deviation Alarm
0- 3276.7
E
C/
E
F
12
V5014
Alarm Deadband
0.1-50.0
E
C/
E
F
13
V5015
Setpoint Low Limit
± 3276.7
E
C/
E
F
14
V5016
Setpoint High Limit
± 3276.7
E
C/
E
F
15
V5017
Input Type
(0=J, 1=E, 2=K, 3=R, 4=S, 5=T)
(6=B, 7=N, 20=C)
(26=0-5V, 27=±5V)
(29=0-156.25mV,
30=±156.25mV)
(8=European Pt100,
9=American)
(10=European Pt1000)
(11=CU-10
S
, 12=CU-25
S
)
16
V5020
PID Control Period
0.5-99.9 seconds
17
V5021
ON/OFF Hysteresis
0.1-3276.7
E
C/
E
F
18
V5022
Temperature Calibration
Adjustment
± 3276.7
E
C/
E
F
19-23
V5023-V5027
Reserved for Future Feature Enhancements
Summary of Contents for Direct Logic 405
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 16: ...INTRODUCTION 1 6...
Page 38: ...INSTALLATION AND WIRING 2 22...
Page 45: ...SUPPORTING LADDER LOGIC 3 7...
Page 47: ...SUPPORTING LADDER LOGIC 3 9...
Page 48: ...SUPPORTING LADDER LOGIC 3 10...
Page 62: ...TROUBLESHOOTING 6 4...