![FACTS Engineering Direct Logic 405 Manual Download Page 15](http://html1.mh-extra.com/html/facts-engineering/direct-logic-405/direct-logic-405_manual_3159079015.webp)
INTRODUCTION
1.5
Voltage Input Specifications
Voltage Ranges
0-5, ±5V, 0-156.25, ±156.25mV
Resolution
16-bit binary (1 in 65536)
Calibration Error
±13 counts typ., ±33 maximum full scale
±1 count maximum offset (0V input)
Maximum Inaccuracy
±.02% typ. ±.2% maximum
Thermocouple Input Specifications
Temperature Ranges
Type J -190/760
E
C (-310/1400
E
F)
Type E -210/1000
E
C (-346/1832
E
F)
Type K -150/1372
E
C (-238/2502
E
F)
Type R +65/1768
E
C (+149/3214
E
F)
Type S +65/1768
E
C (+149/3214
E
F)
Type T -230/400
E
C (-382/752
E
F)
Type B 529/1820
E
C (+984/3308
E
F)
Type N -70/1300
E
C ( -94/2372
E
F)
Type C +65/2320
E
C (+149/4208
E
F)
Input Fault Protection
60 Vrms or 50 Vdc maximum
Cold Junction Compensation
Automatic
Input Impedance
20 M
S
Resolution
±0.1
E
C (Relative accuracy)
Warm-Up Time
30 min. typ. for ±1
E
C repeatability
Maximum Inaccuracy
±3
E
C excluding error of thermocouple
(See page 2.7 for additional sources of inaccuracy)
RTD Input Specifications
RTD Types
European, = .003850, (Pt100 & Pt1000)
American, = .003916, (jPt100)
Copper (CU-10
S
& CU-25
S
)
Temperature Ranges
Pt100, -200.0/850.0
E
C (-328/1562
E
F)
Pt1000, -200.0/595.0
E
C (-328/1103
E
F)
jPt100, -38.0/450.0
E
C (-36/842
E
F)
CU-10/25
S
, -200.0/260.0
E
C (-328/500
E
F)
Input Fault Protection
50 Vdc maximum
RTD Excitation Current
200 µA
Resolution
±0.1
E
C or
E
F
Maximum Inaccuracy
±1
E
C
Summary of Contents for Direct Logic 405
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 16: ...INTRODUCTION 1 6...
Page 38: ...INSTALLATION AND WIRING 2 22...
Page 45: ...SUPPORTING LADDER LOGIC 3 7...
Page 47: ...SUPPORTING LADDER LOGIC 3 9...
Page 48: ...SUPPORTING LADDER LOGIC 3 10...
Page 62: ...TROUBLESHOOTING 6 4...