21
ENGLISH
–
Unwinding the hose:
carefully remove the hose
from the housing; after unwinding the necessary
length of hose, loosen the grip slightly, in this way,
when a “CLICK” is heard, the lock is inserted (fig. 9).
Ensure that the hose is locked before releasing
the grip.
–
Rewinding the hose:
loosen the lock by pulling
the extension hose outwards (fig. 10). Let the hose
rewind in a controlled way, accompanying it until it
completely returns to the reel.
●
Insert the power cord plug into a suitable socket, mak-
ing sure that the
I/O
switch on the compressor is in the
switched off position “
O
” (OFF).
●
At this point the compressor is ready for use.
●
Use the
I/O
switch to start the compressor pumping air
and putting it through the delivery hose into the tank.
●
Once the upper calibration value has been reached
(set by the manufacturer during the test phase) the
compressor stops.
Using air, the compressor restarts automatically when the
lower calibration value is reached (2 bar between upper
and lower value).
●
The compressor continues to operate with this cycle
automatically until acting on the
I/O
switch.
●
If the compressor shall be used again, wait at least 10
seconds from the moment when it switches off before
restarting it.
●
Check that the air consumption and the maximum
operating pressure of the pneumatic tool to be used
are compatible with the pressure set on the pressure
regulator (not included) and with the amount of air
delivered by the compressor.
●
At the end of the work:
–
rewind the hose completely, putting it in its housing;
– stop the compressor by acting on the
I/O
switch,
putting it to the switched off position “
O
” (OFF).
–
disconnect the electrical plug;
– empty the tank.
8. REMOTE PRESSURE REGULATOR
(Fig. 13)
PURPOSE AND USE
This unit has been designed to be used as a PRESSURE
REGULATOR, any other use should be considered
improper. The company declines all responsibility for
damage or accidents resulting from improper use of the
unit or from failure to comply with the safety regulations.
Any tampering or modification of the unint not previously
authorized relieves the manufacturer from damages
deriving from or referable to the above-mentioned acts.
GENERAL SAFETY WARNINGS
RISKS DUE TO IMPROPER USE
●
DO
NEVER
exceed the recommended maximum operat-
ing pressures.
– The unit must only be connected to a source of
compressed air which does not exceed the operat-
ing pressure of 10 bar.
●
ALWAYS
discharge the air pressure before carrying
out the disassembly, cleaning or reassembly of the unit.
Connection
Connect the unit as shown in fig. 14.
Carry out the connection to the compressed air source,
respecting the direction of the air flow, so that it matches
the arrows in figure 14.
Warning!
Ensure that the compressed air system is not under
pressure when connecting the unit.
USE
Working pressure adjustment
The pressure is regulated by the pressure regulator
knob (12). Turn clockwise to increase the pressure and
anticlockwise to decrease it (as shown in Figures 15 and
16).
The value set can be checked on the gauge (11).